4-29
4 Remote I/O Master Communications
CJ-series DeviceNet Units Operation Manual for NJ-series CPU Unit(W497)
4-4 User
-set A
llocation
s
4
4-4-2 Settings thro
ugh De
vice V
a
riab
les f
o
r CJ-s
er
ies Unit (Master Use
r-set Allocations
S
e
tup
Ta
b
le
)
This example uses the following settings for unit number 0.
•
OUT block 1 area and first word: WR (4), 50CH (50)
•
IN block 1 area and first word: WR (4), 100CH (100)
•
Allocation Size Setup Table area and first word: DM (3), 00100 (100)
This example shows user-set allocations for the following slaves.
Example Settings for User-set Allocations through Device Variables
for CJ-series Unit
Node address
Outputs
Inputs
Product
0
16 pts
0 pts
16-pt Transistor Output Terminal
(DRT1-OD16)
1
8 pts
8 pts
8-pt input and 8-pt Output Environment-
resistant Terminal (DRT1-MD16C)
2
16 pts
16 pts
CQM I/O Link Terminal (CQM1-DRT21)
3
0 pts
8 pts
8-pt Transistor Input Terminal (DRT1-
ID08)
4
None
---
5
160 pts
160 pts
CJ-series DeviceNet Unit (CJ1W-
DRM21) (Slave Unit)