4 Remote I/O Master Communications
4-16
CJ-series DeviceNet Units Operation Manual for NJ-series CPU Unit(W497)
z
Step 6: Define the User-defined Variable
Define a user-defined variable for the area to which each slave is allocated. By using the user-
defined variable, the user program can access the allocation area of the slave.
Below is an example of a user-defined variable in which fixed allocations area 1 is selected.
Fixed Allocations Area 1
OUT blocks are allocated to slaves from CIO 3200 to CIO 3263 and IN blocks are allocated to slaves
from CIO 3300 to CIO 3363 in the memory used for CJ-series Unit. To access the output (OUT)
block and the input (IN) block from the user program, allocate a user-defined variable to the applica-
ble area.
CIO Area in memory for CJ-series Units
Bit
Bit
OUT block
IN block
OUT block
Bit
Address 0
IN block
Output to Slaves
Input from Slaves
Address 1
Address 2
Address 60
Address 61
Address 62
Address 63
Address 0
Address 1
Address 2
Address 60
Address 61
Address 62
Address 63
Bit
CIO 3200
to
CIO 3263
CIO 3300
to
CIO 3363
CIO 3200
CIO 3202
CIO 3201
CIO 3260
CIO 3262
CIO 3261
CIO 3263
CIO 3300
CIO 3302
CIO 3301
CIO 3360
CIO 3362
CIO 3361
CIO 3363
to
to
to
to