9-59
9 Troubleshooting and Maintenance
CJ-series DeviceNet Units Operation Manual for NJ-series CPU Unit(W497)
9-4 Even
t L
ogs
9
9-4-3 Error De
scr
iptio
ns
Event name
Invalid Message Timer List Error
Event code
148C 0000 hex
Meaning
The data in the message monitoring timer list is not correct.
Source
PLC Function Module
Source details
CJ-series Unit
Detection
timing
At power ON or
Controller reset
Error attributes
Level
Observation
Recovery
---
Log category
System
Effects
User program
Continues.
Operation
The message monitoring timer will operate with the
default value.
System-defined
variables
Variable
Data type
Name
None
---
---
Cause and
correction
Assumed cause
Correction
Prevention
The power supply was interrupted
while writing the message-monitoring
timer list to the non-volatile memory.
Register the message-monitoring
timer list again.
Do not turn OFF the power supply
while the system is writing the set-
tings.
Attached
information
None
Precautions/
Remarks
You can change the event level to the minor fault level. If you change the level to the minor fault level, the
Recovery
col-
umn above will be changed to “Error reset.”