You can connect only one Master Unit to a network if you specify a COS or cyclic connection
with the use of CX-Integrator. Remote I/O communication errors may occur. In such a case,
therefore, change the system setup so that only one Master Unit is connected to a network.
Precautions
Same as previous net-
works.
•
The communications cycle time
is longer.
Note
The communications cycle
time for the network in the
figure above is TA+TB if sec-
tions A and B above are
separate networks with a
communications cycle time
of TA and TB.
•
Multiple Master Units cannot
share a single Slave Unit.
•
Bus Off errors (communica-
tions stopped by multiple trans-
missions) may occur if multiple
Master Units with disabled scan
lists are present on a single net-
work.
•
Make sure that each word allo-
cated in the system is allocated
to only one Master Unit.
Pattern
One Master Unit con-
nected on a single net-
work
Multiple Master Units con-
nected on a single network
Multiple Master Units con-
nected to a single CPU Unit