30
IR/CIO Area Allocations
Section 3-1
3-1
IR/CIO Area Allocations
3-1-1
Overview
Each ASCII Unit is allocated 10 words in the Special I/O Unit Areas of the
CPU Unit’s IR or CIO Area. The words that are allocated depend on the Unit
No. set on the rotary switch on the front panel of the ASCII Unit. The contents
of the allocated 10 words is exchanged automatically between the CPU Unit
and the ASCII Unit every time the CPU Unit refreshes I/O.
Data Exchange for the C200HX/HG/HE, C200H, C200HS
Note
For CPU Units C200HG-CPU53-E/63-E/53-ZE/63-ZE and C200HX
-CPU54-E/64-E/54-ZE/64-ZE/65-ZE/85-ZE, IR 400 to IR 459 are also allo-
cated (maximum of 16 Special I/O Units).
Special I/O Area Allocation for the C200HX/HG/HE, C200H, C200HS
Note
For C200HG-CPU53-E/63-E/53-ZE/63-ZE and C200HX-
CPU54-E/64-E/54-ZE/64-ZE/65-ZE/85-ZE CPU Units only.
Unit No.
Allocated words
Unit No.
Allocated words
Unit No.
Allocated words
Unit No.
Allocated words
0
IR 100 to IR109
4
IR 140 to IR 149
8
IR 180 to IR 189
C
IR 420 to IR 429
(See note.)
1
IR 110 to IR 119
5
IR 150 to IR 159
9
IR 190 to IR 199
D
IR 430 to IR 439
(See note.)
2
IR 120 to IR 129
6
IR 160 to IR 169
A
IR 400 to IR 409
(See note.)
E
IR 440 to IR 449
(See note.)
3
IR 130 to IR 139
7
IR 170 to IR 179
B
IR 410 to IR 419
(See note.)
F
IR 450 to IR 459
(See note.)
CPU Unit
ASCII Unit
IR Area
Unit 0
Unit 0
Data automatically
exchanged during I/O
refresh
Unit 1
Unit 9
(see note)
IR 100
IR 104
IR 105
IR 109
IR 110
IR 119
IR 190
IR 199
5 words
5 words
15
0
Summary of Contents for C200H-ASC11
Page 1: ...C200H ASC11 ASC21 ASC31 ASCII Units Operation Manual Revised June 2000...
Page 2: ...iv...
Page 4: ...vi...