254
Reading and Clearing the Error Log
Section 9-4
Note
*Of the C200HX/HG/HE CPU Units, used only in the C200HX/HG-CPU5
@
-
(Z)E C200HX/HG-CPU6
@
-(Z)E.
Program memory in the ASCII Unit may be destroyed if the ASCII Unit is
restarted while it is executing startup processing after the power supply is
turned ON. Program restarts so that they will not occur during startup pro-
cessing.
Example:
9-4
Reading and Clearing the Error Log
9-4-1
Overview of Error Log Table
The ASCII Unit has an error log table which contains up to of 30 errors. When
an error occurs, the error code and type are stored in the Error Log Table.
AR 0109
SR 28109
A50209 Restarts Unit 9.
---
SR 28110
A50210 Restarts Unit A (10).*
---
SR 28111
A50211 Restarts Unit B (11).*
---
SR 28112
A50212 Restarts Unit C (12).*
---
SR 28113
A50213 Restarts Unit D (13).*
---
SR 28114
A50214 Restarts Unit E (14).*
---
SR 28115
A50215 Restarts Unit F (15).*
Bit address
Function
C200H/HS
C200HX/HG/HE
CS1
User-defined restart bit
BASIC RUN Flag
Word n+5, bit 07
Special I/O
Unit Restart
Bit
ASCII Unit
Error log
table
Newest
Up to 30
When toggling word n bit 06,
the previous error type/code
is called.
Allocated I/O (n + 7)
When an error is generated, the newest
error type/code is recorded on the Error
Log Table.
New/old error flag
By toggling this bit back and forward between 1 and 0,
the previous error type/code is displayed on the Error
Log Table in n + 7.
Error type/code
Error type/code
Error type/code
Allocated I/O (n + 5)
Allocated I/O (n)
Error type/code
Error type
Error code
Summary of Contents for C200H-ASC11
Page 1: ...C200H ASC11 ASC21 ASC31 ASCII Units Operation Manual Revised June 2000...
Page 2: ...iv...
Page 4: ...vi...