23
Installation
Section 2-2
Mounting Positions and Number of Units
Restrictions on SYSMAC
BUS Slave Racks
The following restrictions apply when mounting Units to SYSMAC BUS Slave
Racks.
PC
CPU Unit
Total No. of Units
on CPU Rack,
Expansion I/O
Racks, and
SYSMAC BUS
Slave Racks
Mounting
restrictions
C200HX/HG/HE
C200HE-CPU11-E/32-E/42-E/11-ZE/32-ZE/42-ZE
C200HG-CPU33-E/43-E/33-ZE/43-ZE
C200HX-CPU34-E/44-E/34-ZE/44-ZE
10
None
C200HG-CPU53-E/63-E/53-ZE/63-ZE
C200HX-CPU54-E/64-E/54-ZE/64-ZE/65-ZE/85-ZE
16
C200HS
C200HS-CPU01-E/01-EC/21-E/21-EC/31-E/03-E/23-E/33-E
10
CS1
CS1H-CPU66-E/65-E/64-E/63-E
CS1G-CPU45-E/44-E/43-E/42-E
16
None
C200H
C200H-CPU01-E/02-E/03-E/11-E/21-E/23-E/31-E
10
Do not mount
Unit to rightmost
two slots on
CPU Rack.
Dimensions
Unit Dimensions when Mounted
Cable
connector
Backplane
connector
35
100.5
117
180 to 200
ASC11
CH
RUN
ERR
T/R 1
ERR 1
BASIC
T/R 2
ERR 2
130
Group
A
B
C
D
Unit
ASCII Unit,
High-speed Counter
Unit, Position Control
Unit (NC111/112/113/
213) Analog I/O Unit,
ID Sensor Unit, Fuzzy
Logic Unit
Multi-point I/O Unit
Temperature Sensor
Unit, Voice Unit
Position Control Unit
(NC211)
Motion Control Unit
Number of Units
mountable for each
group per Remote I/O
Master Unit
4 Units
8 Units
6 Units
2 Units
Number of Units
mountable for all
groups combined per
Remote I/O Master
Unit
3A + B + 2C + 6D
≤
12, and A + B + C + D
≤
8
Summary of Contents for C200H-ASC11