247
List of Error Messages
Section 9-1
PC Interface Errors
DM Setting Errors
Error
code
Error message
Probable cause
Corrective measures
0080
No message.
The IOWR/IORD instruction is
incorrect.
Check the operands for the IOWR/
IORD instructions.
0081
No message.
Incorrect number of transfer (read/
write) words in the IOWR/IORD
instruction.
Set the IOWR/IORD (#00
@@
)
instruction to a maximum of 90 words
and the IOWR/IORD (#FD00)
instruction to a maximum of 128 words.
0082
No message.
Interrupt to the ASCII Unit using the
IOWR (#CC00) instruction is incorrect.
Check whether or not the
IOWR(#CC00) instruction interrupt
number matches the ON PC (interrupt
number) command.
0083
No message.
When reading and writing to the shared
memory using the IOWR/IORD
(#00
@@
) instruction, the first read/write
word (offset word
@@
from the
beginning of the IOWR/IORD Area) is
incorrect.
Check the offset word
@@
in the IOWR/
IORD (#00
@@
) instruction and the first
words of the IOWR Area and IORD
Area (m + 6 and m + 7 in the DM Area
allocations).
0084
---
Not used.
---
0085
No message.
ON PC interrupt number is out of range. Use 01 to 99.
0086
No message.
The PC interrupt number is an illegal
BCD value.
Use a valid BCD value.
0087
---
Not used.
---
0088
---
Not used.
---
0089
---
Not used.
---
Error
code
Error message
Probable cause
Corrective measures
0090
No message.
Incorrect setting for program number at
startup (DM Area allocations).
Set any between 00 and 04 (BCD).
0091
No message.
Incorrect automatic transfer settings
from flash ROM (DM Area allocations).
Set either 00 or 5A
hex
.
0092
No message.
Incorrect Start Mode settings (DM Area
allocations).
Set either 00 or 5A
hex
.
0093
No message.
Incorrect initial value transfer settings
(DM Area allocations)
Set either 0 or 1 (BCD).
0094
No message.
Not used (DM Area allocations).
Set 0 (BCD).
0095
No message.
Incorrect baud rate parameters for port
1, 2, or terminal (DM Area allocations).
Set any of 00 to 08 (BCD).
0096
No message.
Incorrect number of transfer words per
cycle (DM Area allocations).
After checking that the PC is a
C200HX/HG/HE or CS1-series PC, set
either 00 or 5A
hex
.
0097
No message.
Invalid screen size or terminal mode.
Set the specified value within the
proper range.
0098
No message.
The first transfer word setting for the
IORD or IOWR Area is incorrect (DM
Area allocations).
Set either 00, or between 10 and 99
(BCD).
0099
No message.
Invalid DMA option (port 1 or 2)
Set either 00 or 5A
hex
.