Hardware reference
HARDWARE REFERENCE MANUAL
64
Revision 5.0
fig. 12
15. When you design a cabinet for the units, make sure that the cabinet
allows at least 20 mm of space around the units to provide sufficient
airflow. We advise to allow at least 100 mm of space around the units.
3.2.2
Environmental and storage for all units
/i
Duct
20 mm min.
DIN Track
20 mm min.
Unit
Duct
Item
Specification
Ambient operating temperature
0 to 55°C
Ambient operating humidity
10 to 90% RH. (with no condensation)
Ambient storage temperature
-20 to 70°C (excluding battery)
Ambient storage humidity
90% max. (with no condensation)
Atmosphere
No corrosive gases
Vibration resistance
10 to 57 Hz: (0.075 mm amplitude): 57 to 100 Hz:
Acceleration: 9,8 m/s2, in X, Y and Z directions for
80 minutes
Shock resistance
147 m/s
2
, 3 times each X, Y and Z directions
Insulation resistance
20 M
Ω
Dielectric strength
500 VAC
Protective structure
IP20
International standards
CE, EN 61131-2, cULus, Lloyds
RoHS compliant