Page 35
DH1 BASE UNIT / DH2 WIRELESS GATEWAY
USER GUIDE
16.
EDITING GATEWAY PROPERTIES
After making any changes, must update Gateway for changes to
take into effect.
1.
Accessing Gateway properties window
a.
Click on Gateway in project tree and right-click and select “Edit” or
click on “E” button
2.
Radio Tab
a.
Allows adjusting of Tx power level and number of transmission
retries
i.
Higher Tx level consumes more power
3.
Serial/RTU Port Tab
a.
Allows configurations of Serial/RTU port
b.
RTU port can be set as a Modbus Master, Modbus Slave,
LevelMaster ASCII Slave, or ROC-Link Master
c.
Can be configured to RS232 or RS485
d.
Use the appropriate port settings to match with connecting device
e.
When using Gateway as ROC-Link Master, it supports the following
Opcodes:
i.
Opcode 17, Login Request
ii.
Opcode 10, Read Configurable Opcode Point Data
iii.
Allows user to read up to 10 user configurable (TLP) points
from a ROC.
iv.
Points can be a mix of type INT16 (signed or unsigned) or
FL(OAT).
Controlled Copy