![background image](http://html1.mh-extra.com/html/oldham/olct-200/olct-200_user-manual_3711996069.webp)
69
OLCT 200 User Manual |
69
SECTION 9 -
SENSORS
9.1 Catalytic Bead (LEL) Sensors
Factory Default Settings
Ref #
Gas
Range
Resolution
Cal Gas
Low Alarm
High
Alarm
10
Combustible,
LEL, Methane
Cal
0-100%
LEL
1% LEL
50% LEL
10% LEL
20% LEL
11
Combustible,
LEL, Pentane
Cal
0-100%
LEL
1% LEL
25% LEL
10% LEL
20% LEL
12
Combustible,
LEL, Hydrogen
Cal
0-100%
LEL
1% LEL
25% LEL
10% LEL
20% LEL
9.2 Infrared (IR) Sensors
Factory Default Settings
Ref
#
Gas
Range
Resolution
Cal Gas
Low Alarm
High
Alarm
20
CO2
0-5%
Vol
0.1% Vol
2.5% Vol
0.5% Vol
1.0% Vol
21
Methane, LEL
0-100%
LEL
1% LEL
50% LEL
10% LEL
20% LEL
22
Propane, LEL
0-100%
LEL
1% LEL
25% LEL
10% LEL
20% LEL
26
Ethylene, LEL
0-100%
LEL
1% LEL
50% LEL
10% LEL
20% LEL