OLCT 200 User Manual |
26
RS-485 Modbus networks should be wired as shown in Figure 2-11. Each OLCT 200
connected represents an RTU and must have a unique RTU address. RTU addresses
are assigned in the Modbus setup menu described in section 4.10. Cabling must be a
“daisy chain” as opposed to a “star” pattern for reliable operation. The “end of line” unit
should have J1 installed in the ‘A’ position for terminating resistor installation. All
others should have J1 in the ‘B’ position. Front panel Rx / Tx LEDs are helpful
troubleshooting tools.
Figure 2-11: RS-485 Modbus Wiring
2.8 Isolated 4-20mA Output 10-0250 Option
Description:
The optional 10-0250 Isolated 4-20mA option (Figure 2-12) provides dual 4-20mA
outputs that are electrically isolated from sensor inputs and the 24 VDC power source.
Each 4-20mA output share the same common terminal and are not isolated from each
other. This board is “piggybacked” behind the 10-0232 Display Assembly (Figure 2-3).
Addition of this option requires 4-wire mode 4-20mA operation and thereby requires the
I/O Power Supply board (Figure 2-5).
Summary of Contents for OLCT 200
Page 4: ...OLCT 200 User Manual 4...
Page 14: ...OLCT 200 User Manual 14 Figure 2 3a Outline Drawing OLCT 200 Wired Models...
Page 19: ...OLCT 200 User Manual 19 2 6 2 Installation Drawing 11 0100...
Page 32: ...OLCT 200 User Manual 32...
Page 36: ...OLCT 200 User Manual 36...
Page 38: ...OLCT 200 User Manual 38 Figure 4 1 Calibration Gas Input...
Page 61: ...OLCT 200 User Manual 61 Figure 6 5...
Page 62: ...OLCT 200 User Manual 62...
Page 79: ...OLCT 200 User Manual 79...