71
OLCT 200 User Manual |
71
9.2.2
IR-Propane Sensor
The propane IR sensor is factory configured to accurately monitor propane gas. As
seen in Figure 9-2, the cross-sensitivity of the propane IR sensor does permit accurate
measure of other combustible gases via a cross-reference factor. It should be noted
however, that the Propane-IR sensor WILL respond to other combustible gases and is
not Propane specific.
Figure 9-2 Cross-sensitivity chart for OLCT 200 Propane IR Sensor.
The output of the IR sensor can be disrupted by sudden changes in temperature. If
there is an excessive change in the ambient temperature, gas sample temperature or
flow rate, then the output signal will be monmentarily frozen. Correct operation is
restored when the effects of the transient have settled. Rates of change in the ambient
temperature should be restricted to 2
C/minute and gas flow rates kept below 0.6
L/minute.
Extreme pressure variations will cause errors in readings. The unit should be
recalibrated if the atmospheric pressure change is greater than 10% from the orignial
pressure.
Do not expose the sensor to corrosive gases such as Hydrogen Sulphide.
Do not allow condenseation to occur inside the sensor.
Summary of Contents for OLCT 200
Page 4: ...OLCT 200 User Manual 4...
Page 14: ...OLCT 200 User Manual 14 Figure 2 3a Outline Drawing OLCT 200 Wired Models...
Page 19: ...OLCT 200 User Manual 19 2 6 2 Installation Drawing 11 0100...
Page 32: ...OLCT 200 User Manual 32...
Page 36: ...OLCT 200 User Manual 36...
Page 38: ...OLCT 200 User Manual 38 Figure 4 1 Calibration Gas Input...
Page 61: ...OLCT 200 User Manual 61 Figure 6 5...
Page 62: ...OLCT 200 User Manual 62...
Page 79: ...OLCT 200 User Manual 79...