59
OLCT 200 User Manual |
59
with an WX16 Controller as server along with additional Relay Modules,
WX16 and WX4 Clients). RF HANDSHAKING =
ON
always transmits the
packet 4 times and does not require any “acknowledge” returned by the
receivers.
*TX Power
(900MHZ models only) may be set for 10 mW, 200mW, 400mW
and 1 watt. Since
some OLCT 200’s are battery powered the TX Power
setting should be as low as possible to sustain reliable communication. The
maximum TX Power setting is 30db (1 watt) and each time TX power is
reduced by half, antenna transmit power is reduced by 3dB.
2.4GHZ variation: The TX Power menu is not available in 2.4GHZ models
and is fixed at 50mW
.
TX Verbose
is unavailable for firmware revisions 3.09 and earlier.
Wakeup Time
menu is new to firmware revision 3.09 and determines how
often the radio is activated WHEN THERE IS NOT AN A1 or A2 LEVEL
ALARM. The default value is 300 seconds (5 minutes) but this may be
reduced to as low as 6 seconds. Intervals are rounded up to the nearest 6
seconds regardless of the menu entry (example: 50 second entry transmits
every 54 seconds).
IMPORTANT
: More frequent RF transmissions deplete the battery faster!
Radio Status
opens a page indicating if the OLCT 200 is In Range of the
Server. A voltage reading on this page displays the internal 3.3V power
supply value.
TX Multiples
,
RF Handshaking
and
TX Power
menu settings are available to improve
communications reliability by increasing the quantity and power of wireless
transmissions.
IMPORTANT!
Ensure proper selection and location of antennas before increasing
TX
Multiples
and
TX Power
settings! Battery life will be reduced by increasing these
settings. Proper selection and location of antennas contributes much more to
successful communications, without sacrificing battery life, than these settings.
6.5.1
OLCT 200 AND WX16 BASE STATIONS
Figure 6-3 shows correct settings for the WX16
base station’s “Data From” menu
to receive data from
OLCT 200’s
. Each WX16
channel’s Remote ID must match the
OLCT 200’s Remote ID setting (see section 6.7) in order for its VALUE to appear on
the desired WX16 channel. The OLCT 200 counts value equals 75 counts, or -15.6%,
during CAL MODE. Enabling
the WX16’s “INPUT MARKER” menu as shown on the
right menu in Figure 6-3 causes the WX16 to indicate IN CAL when the OLCT 200 has
its CAL MODE activated.
Summary of Contents for OLCT 200
Page 4: ...OLCT 200 User Manual 4...
Page 14: ...OLCT 200 User Manual 14 Figure 2 3a Outline Drawing OLCT 200 Wired Models...
Page 19: ...OLCT 200 User Manual 19 2 6 2 Installation Drawing 11 0100...
Page 32: ...OLCT 200 User Manual 32...
Page 36: ...OLCT 200 User Manual 36...
Page 38: ...OLCT 200 User Manual 38 Figure 4 1 Calibration Gas Input...
Page 61: ...OLCT 200 User Manual 61 Figure 6 5...
Page 62: ...OLCT 200 User Manual 62...
Page 79: ...OLCT 200 User Manual 79...