DIAM4200 ©2018 AUGIER SA.
6021642 DIAM4200 5 to 20KVA rev 1-8.docx
I-22
I.5.1 CONFIGURATION
The “
Configuration
” menu is used to define the basic parameters of the CCR (for example when replacing the
main board):
•
Rated mains voltage in Vrms:
220-230-240380-400-415
•
Rated power in kVA:
5-7.5-10-15-20
•
Number of brightness (Including B0):
from 1 to 8
I.5.2 SETTING
The “
Setting”
menu is used to assign values of current to brightness levels B0 to B7.
•
Minimum value = 1 Arms
•
Maximum value = 6.8 Arms
I.5.2.1 Current range:
The “Regulation Error” warning is triggered if the measured current is outside the ranges defined for each
setting B0 to B7.
Each range is automatically calculated when a setting is changed (as described below) in the following way:
•
Minimum value = Setting
– 100mA
•
Maximum value = S100mA
Nevertheless it is possible to set two limits of the current range manually using the “
Current range
”
menu.
I.5.3 PROTECTIONS
I.5.3.1 LV power monitoring:
Mains voltage
Duration CCR status
Ui < 75% of rated voltage
0s
CCR stops (Power supply Warning)
Ui > 130% of rated voltage
0s
CCR stops (Power supply warning)
Ui < 85% of rated voltage
60s
CCR stops (Power supply warning)
Ui > 120% of rated voltage
60s
CCR stops (Power supply warning)
90% < Ui < 110% of rated voltage
0s
CCR automatically restarts
I.5.3.2
“Open circuit”:
Open Circuit Protection is activated if the output current goes below a defined value (
I level OC
) for
a
defined period
(
Duration OC).
The CCR stops instantly, and the display shows the message “
Open Circuit
”.
Setting
I level OC
and
Duration OC
:
Go into the menu “
Alarms and Warnings”
then “
Open Circuit
”.
I.5.3.3
“Capacitive current detection”:
The standard IEC61822 Ed2 (7.5.1) note an “Open Circuit detection” with a capactive current highest than the
open circuit level value (see above).This protection can be enabled or disabled in the menu
“Options”
and: