II.1.3 CHECKING THE INSTALLATION
In checking the suitability of the electrical installation in which the CCR is to be integrated, the following
points must be observed:
II.1.3.1 Single phase power supply:
This must be compatible with the electrical characteristics of the device as shown on the rating plate and
factory test report.
The rated mains voltage is recorded in the software on the motherboard and is required for calculations.
The configured rated voltage can be seen in the “
Configuration
” menu, and written on the identification
plate, on the front panel.
See paragraph I.3.3 for the electrical characteristics of DIAM CCRs.
II.1.3.2 LV Protection:
The switchboard of the sub-station containing the regulators will have to include individual and lockable
isolating devices, allowing the visible consignment of each regulator.
When these devices are associated to LV protection, that LV protection for each CCR must be
proportioned according to the power of the CCR, the rated voltage and the type of protection already present on
the CCR.
The following tables are given for information only, for cable lengths between fuse boxes and CCRs of less than
30m (Circuit breaker examples : MG references)
230V Power Supply
400V Power Supply
Power
LV cable gauge
LV circuit breaker
LV cable gauge
LV circuit breaker
5 kVA
10 mm²
IC60N 50A C
6 mm²
IC60N 25A C
7,5 kVA
16 mm²
IC60N 63A D
10 mm²
IC60N 40A C
10 kVA
16 mm²
C120N 100A D
10 mm²
IC60N 50A C
15 kVA
25 mm²
C120N 125A D
16 mm²
C120N 100A D
20 kVA
50 mm²
CVS250B 200A
16 mm²
C120N 100A D
II.1.3.3 Lighting loop:
Check that the installed power corresponds to the power of the CCR, check the continuity of the loop and
the number of lamps blown.
The rated output power is recorded in the software on the motherboard and is required for calculations.
The configured rated power can be seen in the “
Configuration
” menu
II.1.3.4 Management by remote control:
Check the remote control mode: dry contact/external voltage/serial network. For external voltage mode
(multiwire interface), check that the remote control voltage is compatible with the electrical characteristics of the
CCRs.
See paragraph I.3.3 for the electrical characteristics of the DIAM CCRs.
See paragraph II.1.3.4 in order to configure the remote control mode.