The number of fault lamps can be seen in the “
Monitoring”
menu
Two comparison levels (warnings level 1 & 2) are available. They are preferably fixed at 5 and 10.
Setting
Level LFD1 and Level LFD2
parameters:
Go into the menu “
Alarms and Warnings”
then “
Burnt
Lamps Fault
”.
Remote back indication:
•
Each level reached is indicated by a dry contact output
•
The number of fault lamps, levels and warnings are transferred to the Jbus table.
To reset the stored values (for 0 and X lamp burned) during learning. Go in the menu “Calibration” then:
When press ‘OK’, learning is resetting and to determine the number of burnt lamps in the output load, it is
necessary to realize a new learning calibration (for 0 and X lamp burned).
I.8.6 TIME METERS:
This option performs time measurement for :
•
Running time for each brightness,
•
Total working time
•
CCR is powered ON
•
Elapsed time : The total running time is compared to an internal value (set preferably to 1000H).
When reached, back indication is sent by a dry contact output, and information set in the Jbus
table.
I.8.7 BUZZER
The CCR can be provided with a sound alarm: when fault occurs, the buzzer will sound. To stop the
noise, it is mandatory to acknowledge the fault (by pressing RESET).
I.8.8 WIG WAG
The CCR can operate in wig wag mode (LAHSO applications), activating the option flag in the “
Option”
menu.
In the menu “
Wig Wag
”, it is possible to modify the “
WigWag tcycle
” and the "
WigWag ton
".
t cycle
t on
B0