62 | DE
OBO Bettermann
Mounting variants
Installation of the touch protection
Always route the isCon
®
conductor Pro+ 75 GR so that it is vertical and
remove any soiling on the conductor.
1. In the area to be protected, route the isCon
®
conductor Pro+ 75 GR to
a length of at least 2.5 m plus the separation distance (s). This corres-
ponds to a length of approx. 3–5 m.
1
Note!
With an increasing length of the isCon
®
conductor Pro+ 75 GR, the con-
tact voltage occurring in the earth also increases.
2. Remove the grey external jacket 0.5 m below the connector (see “7.1.2
Stripping the grey external jacket (isCon Pro+ 75 GR)” on page 30)
and fasten the first conductor holder (type isCon H VA) directly on
solid masonry.
2
If a direct connection to solid masonry is not possible, a separate
potential connection must be made using an earthed rain gutter or
parapet.
3. Attach all further conductor holders (type isCon H 26 VA) at a dis-
tance of ≤ 1 m.
3
4. Maintain the minimum bend radius of 260 mm.
4
Fig 66:
1
2
3
0,5 m
≤ 1 m
2,5 m
s
e
5408 056
5311 519
r
260 mm
4
2146 207
≤
Installation of the isCon
®
conductor Pro+ 75 GR as touch protection