Mounting instructions isCon
®
lightning protection system
Mounting variants
8 3
Internal and external isCon
®
conductor
The mounting example shows the use of an isFang air-termination rod
with internal isCon
®
conductor
1
, to which a second, external isCon
®
conductor
2
is connected.
Note!
When using the grey isCon
®
conductor, the light grey external jacket
must be removed before connecting the potential connection (see “7.1.2
Stripping the grey external jacket (isCon Pro+ 75 GR)” on page 30).
The potential connection clip
3
(type 927 2 6-K) must be mounted, in
order to create an electrical connection between the black, weakly con-
ductive layer or protective jacket of the external isCon
®
conductor and the
air-termination rod. The potential is connected here. The internal poten-
tial connection element then means that the internal isCon
®
conductor is
also connected with the potential connection. Alternatively, the potential
can be connected at the air-termination rod stand
4
, provided that the
potential connection clip
3
is mounted.
Fig 63:
2
3
4
1
Internal and external isCon
®
conductor