Mounting instructions isCon
®
lightning protection system
Installing the isCon® system
Fig 30:
Attaching the internal potential connection element
Note!
The internal potential connection element consists of two half shells.
These must be located in such a way that they surround the isCon
®
con-
ductor and one of the half shells is located centrally beneath the screw
holes, so that it can be pressed using the side screw (see also Fig. 33 on
page 38).
4. Place the two half shells of the potential connection element on the
conductor and push them into the retaining pipe.
Fig 31:
Pushing the retaining rod into the central rod
5. Push the retaining rod as far as it will go into the central rod. In so
doing, the opening for the left copper screw (see Fig. 33 on page
38) may not point to the gap between the half shells of the potential
connection, but centrally to one of the half shells. If necessary, turn
the half shells accordingly.
Fig 32:
20 Nm
Fixing the air-termination rod in the central mast