61 | DE
Mounting instructions isCon
®
lightning protection system
Mounting variants
8 5
isCon
®
conductor included in the ring conductor
In areas in which a conventional ring conductor would be difficult in-
stall whilst maintaining the required separation distance (s) (e.g. to roof
structures) (see Fig. 65 on page 61 No.
2
), the isCon
®
conductor
1
can be integrated into the mesh, provided that the calculated separation
distance is less than or equal to the equivalent separation distance of the
isCon
®
conductor used.
Fig 65:
s
s
s
s
s
1
2
Including the isCon
®
conductor in a conventional ring conductor
Legend
1
isCon
®
conductor
2
Conventional ring conductor with separation distance s
8 6
Touch protection
The isCon
®
conductor Pro+ 75 GR can be used as protection against
dangerous contact voltage. This is particularly required in areas with
groups of people. The isCon
®
conductor Pro+ 75 GR was tested up to a
length of max. 5 m with a pulse voltage of min. 100 kV (1.2/50 μs) in rain
and fulfils the requirements for touch protection according to VDE 0185-
305-3 (IEC/EN 62305-3).
Risk of electric shock!
Energised parts
Replace metallic rain gutters, in direct proximity to the isCon
®
conductor Pro+ 75
GR, with plastic pipes.
Risk of damage!
When multiple concrete bases are used, the heavy weight can lead to damage
to the substrate.
If necessary, place protective mats under the concrete base.
WARNING