40 | DE
OBO Bettermann
Installing the isCon® system
Fastening the isCon
®
conductor on the air-termination rod
Note!
Before assembling the air-termination rod, the isCon conductor must be
prepared in the manner described in “7.1 Preparing the isCon® conduc-
tor” on page 30 and a connection element mounted as described in
“7.2 Mounting isCon connection elements” on page 32.
For one isCon
®
conductor:
Fig 36:
24 Nm
Mounting the connection plate for one isCon
®
conductor on the air-termination
rod
1. Mount the connection plate (type isCon AP1-16 VA) at the bottom end
of the air-termination rod, as shown in Fig. 36. Tightening torque:
24 Nm.
2. Mount the connection element of the isCon
®
conductor on the con-
nection plate. Tightening torque: 24 Nm.
For multiple isCon
®
conductors
Fig 37:
24 Nm
Fastening multiple isCon
®
conductors on the mast
1. For 2 isCon conductors, use the connection plate for 2 conductors
(type isCon AP2-16 VA). When connecting 4 conductors, mount 2
connection plates over each other (see Fig. 37).
2. Mount the connection element of the isCon
®
conductor on the con-
nection plate. Tightening torque: 24 Nm.
3. Run the conductors downwards on the air-termination rod, ideally
opposite one another (see Fig. 37).
4. Install the conductors as far apart from each other as possible, if the
installation conditions permit this.