Troubleshooting
OCM F - rev. 05 / 06.04.2018
page 93
Error
Possible
Reason
Correction
Display >Error
Doppler Sensor<
Connection
Check cable connection.
Wiring on terminal strip switched?
Cables firmly connected to plugs (re-tighten
screws, pull at cable ends)?
Insulation of single wires unintentionally clamped
in?
Communica-
tion
Communication to sensor disturbed.
Can be checked by choosing menu I/O >v-Sensor
Info<. Sensor should be indicated in the first line of
the following screen.
Check cables for interruption or loose connection.
Check sensor for mechanical damage.
Unstable
measurement
values
Hydraulically
unsuitable
measurement
place
Check quality of measurement place by using the
graphic flow profile display.
Relocate the sensor to a hydraulically more suita-
ble place (extend calming section).
Remove soiling, sedimentation or obstructive con-
structions in front of the sensor.
Straighten the flow profile by installing appropriate
baffle plates and calming elements, flow straight-
eners or similar upstream of measurement.
Increase damping.
Sensor
Check sensor position (towards flow direction,
horizontal installation) and correct installation
depth.
Check sensor for sedimentation or obstructions.
Summary of Contents for OCM F
Page 105: ...Approvals and Certificates OCM F rev 05 06 04 2018 page 105 Approvals and Certificates...
Page 106: ...Instruction Manual OCM F page 106 OCM F rev 05 06 04 2018...
Page 107: ...Approvals and Certificates OCM F rev 05 06 04 2018 page 107...
Page 108: ...Instruction Manual OCM F page 108 OCM F rev 05 06 04 2018...
Page 109: ...Approvals and Certificates OCM F rev 05 06 04 2018 page 109...
Page 110: ...Instruction Manual OCM F page 110 OCM F rev 05 06 04 2018...