ID300/302 Integrated Motor Drive |
Start Up Tips for the ID300/302
5
1 Start Up Tips for the ID300/302
Read the entire manual before attempting any of the following Tips. These Tips are intended to simplify
the startup of the ID300/302 unit. Make sure to install the unit in an environment that falls within the
environmental conditions outlined in this manual. In addition, confirm that all wiring and fusing is per the
manual, the National Electrical Code and all State and Local codes.
1.1 Jumper Wire
A jumper wire or strap must be installed between
Terminals 6 and 8
to allow the ID300/302 to be
started. Without the jumper wire, the RTC Keypad will display “Inhibit.” Make sure the main electrical
power is switched off and locked out before removing the ID300/302 top cover. It is easier to remove
the terminal blocks above the one that includes
Terminals 6 and 8
to install the jumper wire. Reinstall
the terminal blocks in the reverse order. Refer to Section 4.2 on
page 23
for location of the terminal
blocks.
1.2 RTC Keypad and Cable
The standard factory programming of the ID300/302 unit is to use the
remote RTC keypad and cable. The cable needs to be routed through one
of the ports on the side flange of the ID300/302 unit by removing one of the
plastic plugs and installing a cable gland designed for the RJ45 cable plug
to slide through.
The Cable plugs into the internal RJ45 connector.
Refer to picture below for location.
1.3 0 Menu
The ID300/302 has 22 menus of parameters that can be tailored to a customer’s application. The
ID300/302 has a custom program installed that tailors the unit to the motor rating and sets
0 Menu
parameters to a custom configuration as shown beginning on
page 38
.
If the operation of the unit does not match your application, then the keypad can be used to change
a parameter and save the new setting into memory. Refer to the procedure on the next page for a
simplified approach to programming the ID300/302.