ID300/302 Integrated Motor Drive |
Quick Start Commissioning
5 Quick Start Commissioning
This section details the commissioning of
STANDARD Keypad configuration
, which is the default. If
this configuration is not suitable for the application, refer to Section 5
http://www.leroy-somer.com/documentation_pdf/5512_en.pdf.
• Ensure that no damage or safety hazard could arise from the motor starting unexpectedly.
• By default, the correct motor rated current is set in
Pr 05.007
.
DO NOT
alter the rated current.
Otherwise, it will affect the thermal protection of the motor.
•
If the intended maximum speed affects the safety of the machinery, additional independent over-
speed protection must be used.
•
The ID300/302 has low DC bus capacitance (film capacitors) which can induce voltage ripple on
the DC bus with low load conditions. The default settings of the drive address this phenomenon.
For more dynamic applications, it is advisable to adapt the setting.
5.1 Use of a Field Keypad RTC or ID-SIZE 1or ID-SIZE 3-Keypad
•
If the drive is started using a Keypad, it will run to the speed defined by a keypad reference.
Depending on the application, the keypad reference may not be acceptable. The user must check
in Pr 01.017 and ensure that the keypad reference has been set to 0.
If the default settings of the ID300/302 standard configuration are not suitable for the application, the
parameters can be modified using the Keypad option. Commands can be given from the Keypad using
the factory preset configuration. Refer to Section 5.1.6 on page 37 for additional information.
To connect the Keypad, refer to the relevant Keypad installation sheet for more details.
5.1.1 Understanding the Display
WARNING
!
WARNING
!