www.usmotors.com
ID300/302 Integrated Motor Drive |
Quick Start Commissioning
37
5.1.6 Quick Commissioning with a Keypad
Control Connection
Follow control connection diagrams described in Section 5.2.1 on
page 38
.
Quick Start-Up
• Make the required power connections and control connections as indicated above. Refer to
Section 4.5 on
page 27
.
• Ensure that the drive is disabled (Terminal 8 or Terminals 31 and 34 are open).
• Power up the drive.
• Close the Enable Terminal 8 or the STO Terminals 31 & 34.
• Give a Run Forward (or Run Reverse if available) command by pressing the dedicated key on the
keypad.
• Adjust the frequency reference by pressing the
Up
key on navigation keys until the correct speed
reference is reached. (The last setting for speed is saved and applies the next time it is started.)
• Stopping the motor: press the
Stop
key for the motor to stop under ramp control, or remove the
Enable
signal by opening Terminal 8 or Terminals 31 & 34. The motor will then coast to a stop.
For more details about Keypad or keypad ref configurations,
refer to Section 5 http://www.leroy-somer.com/documentation_pdf/5512_en.pdf
Keypad Status Indications
When the drive is in ‘trip’ condition, the upper row of the display will indicate that the drive has tripped.
The lower row of the display will show the trip code. For further information regarding trip codes, refer to
Section 6.1 on
page 41
.
During an ‘alarm’ condition, the upper row of the display alternates between the drive status (Inhibit,
Ready or Run, depending on what is displayed) and the alarm. For further information regarding
alarms, refer to Section 6.2 on
page 43
.
Upper Row String
Description
Drive Output Stage
Inhibit
The drive is inhibited and cannot be run.
Disabled
Ready
The drive is ready to run. The drive enable is active.
Disabled
Stop
The drive is stopped / holding zero frequency.
Enabled
Run
The drive is active and running.
Enabled
Supply Loss
Supply loss condition has been detected.
Enabled
Deceleration
The motor is being decelerated to zero frequency
because the final drive run has been deactivated.
Enabled
DC Injection
The drive is applying DC injection braking.
Enabled
Trip
The drive has tripped and no longer controlling the
motor. The trip code appears in the lower display.
Disabled
Under Voltage
The drive is in the under voltage state.
Disabled
Heat
The motor pre-heat function is active.
Enabled