ID300/302 Integrated Motor Drive |
Connections
27
4.5 Power Connections
• The motor must be connected to earth. Grounding must be performed in accordance with National
Electrical Code and local electrical codes.
•
Due to large leakage current, a permanent fixed ground connection must be provided to the
system by using a 10 mm2 (7 AWG) flat braid.
•
Check that the terminal block has been removed from its fixed holder (unplugged) before making
any connections to avoid putting pressure on the card.
Standard Drive Power Connections
230V or 400V-3ph: Connect to L1, L2, L3
WARNING
!