HMI Bypass Controller Installation and Commissioning Guide
2.5.4 Control Circuit Wiring
2.5.4.1 Analog Input
A 4 to 20 mA analog input signal is available by connecting to the customer
terminals 5 (+) and 4 (-).
Terminal No.
Description
4
0V Common Analog
5
Speed/Frequency Reference
2.5.4.2 Digital Inputs
The HMI bypass combines digital inputs from the HVAC H300 VFD and SI-I/O
option module. As per the following table, the HMI bypass control provides
ten (10) digital inputs.
There are ten (10) digital inputs. (24 Vdc).
Terminal No.
Description
1 (3 positions)
0V Common
22
Fireman’s Override
23
Damper Feedback
24
Fire Alarm
25
Customer Reset
27
Auto Run
29
Enable
203
Safety
204
Relay Output Select (223)
207
Remote Bypass Select
208
Remote VFD Select
Terminal 204 is used as an input signal to control terminal 223 relay output
when terminal 223 is set to “T204 24V Input”. All digital inputs are dry
contacts (voltage free).
2.5.4.3 Relay Outputs
There are two (2) form A relay outputs.
Terminal No.
Description
221
System Fault
222
0V Common for dry contacts 221 & 223
223
System On or 204 24V Input
When Relay Output Select is set up for “204 24V Input” terminal 223 will be
controlled by the input on terminal 204.
Summary of Contents for Control Techniques HVAC Drive H300 HMI Bypass
Page 17: ...HMI Bypass Controller Installation and Commissioning Guide 17...
Page 53: ...HMI Bypass Controller Installation and Commissioning Guide 53 Notes...
Page 54: ...54 HMI Bypass Controller Installation and Commissioning Guide Notes...
Page 55: ...HMI Bypass Controller Installation and Commissioning Guide 55 Notes...