HMI Bypass Controller Installation and Commissioning Guide
3.2.3 Advanced VFD Settings
The Advanced VFD Settings menu allows access to advanced settings of the
VFD.
Voltage Boost
: Defines the level of voltage boost at 0Hz when using a fixed V
to F relationship.
Current Limit
: Limits the current when the motor is being accelerated or
decelerated.
Open-Loop Control Mode
: Defines the VFD output mode. The default setting
for Open-Loop Control Mode is “Fixed” or V/Hz.
• Ur S
: Resistance compensation, stator resistance measured at each start.
• Ur
: Resistance compensation with no stator resistance measurement.
• Fixed
: (Default) Fixed boost with a linear characteristic. Also known as V/
Hz Boost mode.
• UR Auto
: Resistance compensation, stator resistance measured on the first
start.
• Ur I
: Resistance compensation, stator resistance measured at power-up.
Also known as Open-Loop Vector mode.
• Square
: Fixed boost with square characteristic. Also known as Quadratic
Motor V/Hz mode.
• Current 1P
: Single phase current output.
Note: For further information on Open-Loop control modes refer to the HVAC
H300 User Guide.
Reverse Motor Direction
: If Reverse Motor Direction is on, the output phase
sequence is reversed so that the phase sequence in W-V-U for positive
frequencies and U-V-W for negative frequencies.
Dynamic V to F
: Dynamic V to F is intended for applications where power
loss should be kept to a minimum under low load conditions, but dynamic
performance is not important. The setting is enabled by default.
Summary of Contents for Control Techniques HVAC Drive H300 HMI Bypass
Page 17: ...HMI Bypass Controller Installation and Commissioning Guide 17...
Page 53: ...HMI Bypass Controller Installation and Commissioning Guide 53 Notes...
Page 54: ...54 HMI Bypass Controller Installation and Commissioning Guide Notes...
Page 55: ...HMI Bypass Controller Installation and Commissioning Guide 55 Notes...