HMI Bypass Controller Installation and Commissioning Guide
39
Step 2 – Motor Data
: Enter motor nameplate information in the following
settings.
• Rated Frequency
: Motor nameplate value
• Current
: Motor nameplate value
• Speed
: Motor nameplate value
• Voltage
: Motor nameplate value
• Power Factor
: Motor nameplate value
Once complete press the “NEXT” icon.
Step 3 – Motor Ramps/Limits
: Enter the necessary settings for the application.
Once complete press the “NEXT” icon.
Step 4 – I/O Settings
: Verify the Analog Speed Reference mode matches the
HMI Bypass system analog speed/frequency reference type.
Once complete press the “NEXT” icon.