50
HMI Bypass Controller Installation and Commissioning Guide
To configure a drive to HVAC Drive H300 HMI Bypass factory defaults
(examples: replacement VFD or existing VFD that is reset to HVAC Drive H300
defaults), from the System Settings screen select the
Default Settings
icon.
Select “YES” to restore the HVAC Drive H300 HMI Bypass to system defaults.
Select “NO” to return to the SYSTEM SETTINGS Screen.
Warning: Selecting “YES” will reset the HVAC Drive HMI Bypass to factory
default settings and the Setup Wizard must be completed again.
6.5 HVAC Drive H300 HMI Bypass Parameter Defaults
The following table represents the parameter differences of an HVAC Drive
H300 HMI Bypass and a standalone HVAC Drive H300 parameter defaults.
These do not include user settable HMI Bypass settings.
VFD
Paremeter
Parameter
Description
HMI
Bypass Value
HVAC Drive
H300 Default
01.014
Reference Selector
A2 Preset
A1 A2
01.021
Preset Reference 1
15.0 Hz
0.0 Hz
01.023
Preset Reference 3
20.0 Hz
0.0 Hz
01.052
Hand/Off/Auto Operating Mode
0
1
01.053
Fire Mode Reference
40.0 Hz
0.0 Hz
02.004
Ramp Mode
Std boost
Standard
02.008
Standard Ramp Voltage
Drive rating
Drive rating
02.011
Acceleration Rate 1
20.0 s
10.0 s
02.021
Deceleration Rate 1
20.0 s
10.0 s
04.015
Motor Thermal Time Constant 1
120.0 s
89.0 s
04.016
Thermal Protection Mode
0x0
0x1
04.037
Motor Thermal Time Constant 2
50.0 s
89.0 s
05.007
Rated Current
Drive rating
Drive rating
05.008
Rated Speed
Drive rating
Drive rating
Summary of Contents for Control Techniques HVAC Drive H300 HMI Bypass
Page 17: ...HMI Bypass Controller Installation and Commissioning Guide 17...
Page 53: ...HMI Bypass Controller Installation and Commissioning Guide 53 Notes...
Page 54: ...54 HMI Bypass Controller Installation and Commissioning Guide Notes...
Page 55: ...HMI Bypass Controller Installation and Commissioning Guide 55 Notes...