3.1.3.2 Additional Drive Status
This screen displays the estimated total running cost of the HMI bypass system
and filter change reminders.
Power Consumption
: Displays the current power consumption of the VFD.
Power Cost per kWhr
: Defines the cost of energy per kWh in cents.
Total Power Consumption
: Displays the accumulated VFD power consumption.
Total Running Cost
: Uses the Total Power Consumption and Power Cost per
kWhr to calculate Total Running Cost.
3.1.3.3 Trip Log
The previous 5 system faults are recorded and displayed. For accurate
timestamps, the time must be manually set in the HMI settings menu.
Clear Log
: Pressing this button will clear the recorded fault list.
• Motor Overload/PL: Motor thermal overload relay (resettable) or phase
loss monitor (if fitted) is tripped connecting 24V to terminal 26 or VFD
parameter 18.035 is set to 1 via serial communications.
Recommended actions:
»
Check Motor
»
Check Insulation, phase to phase, and phase to ground
»
Check Bearings
»
Check Load/transmission
»
Check for Phase loss or phase loss monitor (if fitted)
»
Reduce Starts per hour
»
Check Motor winding configuration (delta or wye)