HMI Bypass Controller Installation and Commissioning Guide
3.2.12 Alarm Response - Fireman’s Override
This Alarm Response screen allows for the configuration of the Fireman’s
Override feature.
Fireman’s Override
: When enabled, a fireman override command will ignore
“Motor Overload” and “Damper Timeout” faults. The system will still wait for
a damper feedback, but if no feedback is detected and a timeout is triggered,
the system will bypass anyway. The system will run to destruction as long as
the override command and safety input (terminal 203) are present.
Note: When disabled, “Motor Overload” and “Damper Timeout” will stop the
motor.
Firemans’s Override (VFD mode):
If ON, a Fireman’s Override command will
initiate VFD operatin rater than turning the bypass contactor on.
VFD Override Setpoint
: Determines the frequency reference used by the VFD
when in override mode.
Fireman’s Override PID Control:
Allows PID control loop to regulate frequency
reference in override mode (ignores VFD Setpoint frequency).
Note: Fireman’s Override (VFD mode) must be ON for Fireman’s Override PID
Control to function (requires analog input to terminal 6 of VFD).
3.2.13 Advanced I/O Settings
The Advanced, I/O Settings screen, allows the setup of the I/O settings needed
for the onboard PID feature
Analog PID Feedback Mode
: Defines the input mode for analog input 2 (PID
feedback input) VFD terminal 6.
Sensor Range
: Defines the operating range of the feedback sensor. This
information can be found in the documentation provided with your sensor.
Summary of Contents for Control Techniques HVAC Drive H300 HMI Bypass
Page 17: ...HMI Bypass Controller Installation and Commissioning Guide 17...
Page 53: ...HMI Bypass Controller Installation and Commissioning Guide 53 Notes...
Page 54: ...54 HMI Bypass Controller Installation and Commissioning Guide Notes...
Page 55: ...HMI Bypass Controller Installation and Commissioning Guide 55 Notes...