HMI Bypass Controller Installation and Commissioning Guide
13
There is one (1) form C relay output.
Terminal No.
Description
71
0V Damper Control Contact Common
74
Damper Control Contact (NO)
2.5.4.4 Digital Output
There is one (1) digital output. (24 Vdc).
Terminal No.
Description
202
Auto Mode Selected
2.5.4.5 Additional HVAC H300 VFD Connections
Additional analog inputs and outputs are available by making connections
directly to the HVAC H300 VFD. The following connections are located on the
VFD and not the customer connection terminal block.
VFD Terminal No.
Description
4
0V Common Analog Input
6
Analog PID Feedback
VFD Terminal No.
Description
7
Speed/Frequency Output
8
Analog Torque Output
9
0V Common Analog Output
For further information see HVAC Drive H300 User Guide.
2.5.4.6 Additional SI-I/O Connections
Additional Analog I/O and Digital I/O can be made by making connections
directly to the SI-I/O module mounted in slot 3 of the HVAC Drive H300. The
following connections are not found on the customer connection terminal
block.
SI-I/O Terminal No.
Description
205
Digital Input/Output 4
206
0V Common SI-I/O
209
Analog Input 3/Digital Input 7
210
0V Common SI-I/O
211
Analog Output 1/Digital Input 8
Summary of Contents for Control Techniques HVAC Drive H300 HMI Bypass
Page 17: ...HMI Bypass Controller Installation and Commissioning Guide 17...
Page 53: ...HMI Bypass Controller Installation and Commissioning Guide 53 Notes...
Page 54: ...54 HMI Bypass Controller Installation and Commissioning Guide Notes...
Page 55: ...HMI Bypass Controller Installation and Commissioning Guide 55 Notes...