HMI Bypass Controller Installation and Commissioning Guide
29
Auto-Reset Delay
: The time interval between reset attempts. The HMI Bypass
default is 5 seconds.
Hold Drive Healthy
: If set to “ON,” the fault alarm relay will not close until all
reset attempts have been exhausted.
Note: If Hold Drive Healthy is set to “ON” and if Number of Auto-Reset
Attempts is set to “6” (infinite) the Drive Healthy status will always remain
“Healthy.”
3.2.8 Remote Control
The Remote Control screen defines whether the HMI Bypass is controlled by
the customer terminal block inputs or serial fieldbus communications.
This screen allows you to select either “Local” or “Remote” (Serial/Ethernet
communications) control for each individual input. If Remote is selected, the
bypass system will be controlled by the corresponding bit in the VFD rather
than the digital input. Parameter’s referenced below can only be accessed
directly from the HVAC Drive H300 with a keypad or with Connect VFD
configuration software. For further information on Remote setup see the
HVAC Drive H300 User Guide.
Remote
Local
Input
Parameter
Terminal
Fireman Override*
18.031
22
Damper Feedback
18.032
23
Fire Alarm
18.033
24
Reset
18.034
25
Forward/Reverse**
18.037
-
Motor Overload
18.035
26
Auto Run
18.036
27
*Remote Fireman’s Override is only available if Fireman’s Override VFD mode
is off. Remote control will then initiate a bypass run.
**Foreword/Reverse is a remote parameter only used to reverse a running
motor using configured ramps.
SERIAL COMMS:
Navigates to the serial communication configuration screens.
Summary of Contents for Control Techniques HVAC Drive H300 HMI Bypass
Page 17: ...HMI Bypass Controller Installation and Commissioning Guide 17...
Page 53: ...HMI Bypass Controller Installation and Commissioning Guide 53 Notes...
Page 54: ...54 HMI Bypass Controller Installation and Commissioning Guide Notes...
Page 55: ...HMI Bypass Controller Installation and Commissioning Guide 55 Notes...