background image

English – 

15

English

06. 

In 

table A

 below, select the box corresponding to the intersection of 

the row with the value of Ed and the column with the value of K. The 

box contains the maximum possible number of cycles per day (e.g. 

Ed= 2800 and K= 105; daily cycles ≈ 22).

If the number obtained is too low for the intended use or is located in the 

“area not recommended for use”, 2 or more photovoltaic panels may be 

considered, or use of a photovoltaic panel with a higher power. Contact 

the Nice technical assistance service for further information.
The method described, allows you to calculate the maximum possible num-

ber of cycles 

per day

 that the automation is capable of carrying out, accord-

ing to the solar energy supplied. The calculated value is considered an aver-

age value and the same for all days of the week. Considering the presence 

of the battery, which acts as an energy “accumulator”, and the fact that the 

battery also provides automation autonomy for long spells of bad weather 

(when the photovoltaic panel produces very little energy) it may be possible to 

exceed the calculated maximum possible number of cycles per day, provided 

that the average of 10-15 days remains within the envisaged limits.

Table B

 below shows the maximum possible number of cycles, accord-

ing to the 

severity index

 (K) of the manoeuvre, using 

the stored solar 

energy

 of the accumulator. It is considered that initially the battery is 

completely charged (e.g. after a prolonged period of good weather or 

recharging via the optional PCB power supply unit) and that the manoeu-

vres are performed within a period of 30 days.
When the battery runs out of the stored energy, the led starts to indicate 

the battery low signal by flashing briefly every 5 seconds, accompanied 

by a “beep”.

TABLE A - Maximum possible number of cycles per day

 

Ed 

K≤75 

K=100 

K=125 

K=150 

K=175    K=200 

K=225 

K=250 

K=275 

K=300 

K≥325

 

9500

 

123 

92 

74 

61 

53   46 

41 

37 

33 

31 

28

 

9000

 

116 

87 

70 

58 

50   44 

39 

35 

32 

29 

27

 

8500

 

109 

82 

66 

55 

47   41 

36 

33 

30 

27 

25

 

8000

 

103 

77 

62 

51 

44   39 

34 

31 

28 

26 

24

 

7500

 

96 

72 

58 

48 

41   36 

32 

29 

26 

24 

22

 

7000

 

89 

67 

54 

45 

38   34 

30 

27 

24 

22 

21

 

6500

 

83 

62 

50 

41 

35   31 

28 

25 

23 

21 

19

 

6000

 

76 

57 

46 

38 

33   29 

25 

23 

21 

19 

18

 

5500

 

69 

52 

42 

35 

30   26 

23 

21 

19 

17 

16

 

5000

 

63 

47 

38 

31 

27   24 

21 

19 

17 

16 

14

 

4500

 

56 

42 

34 

28 

24   21 

19 

17 

15 

14 

13

 

4000

 

49 

37 

30 

25 

21   19 

16 

15 

13 

12 

11

 

3500

 

43 

32 

26 

21 

18   16 

14 

13 

12 

11 

10

 

3000

 

36 

27 

22 

18 

15   14 

12 

11 

10 

8

 

2500

 

29 

22 

18 

15 

13   11 

10 

7

 

2000

 

23 

17 

14 

11 

10  9 

5

 

1500

 

16 

12 

10 

7   6 

 

1000

 9  7  6 

TABLE B - Maximum number of cycles using exclusively battery power

  K≤75 

K=100 

K=125 

K=150 

K=175 

K=200 

K=225 

K=250 

K=275 

K=300 

K≥325

 741 

556 

445 

371 

318 

278 

247 

222 

202 

185 

171

Area of use not recommended

9.3 - ADDING OR REMOVING DEVICES

Devices can be added to or removed at any time.

Warning! – Do not add devices before you have checked that they 

are fully compatible with the control unit and the motor it controls; 

for details please refer to the NICE Support Service.

9.3.1 - ECSbus

ECSbus is a system that enables connections of ECSbus devices using 

just two wires, which convey both electrical power and communication 

signals. All devices are connected in parallel on the same 2 wires of the 

ECSbus; each device is recognised individually as it is assigned a unique 

address during installation.
Photocells and other devices using this system can be connected to 

ECSbus, such as safety devices, control buttons, indicator lights etc. For 

information about ECSbus devices, see the Nice Home product cata-

logue or visit www.niceforyou.com.
A special learning phase enables the control unit to recognise all con-

nected devices individually, and enables precise diagnostics procedures. 

For this reason, each time a device connected to ECSbus is added or 

removed, the learning phase must be performed on the control unit; see 

paragraph 10.3.3 “Learning other devices”.

9.3.2 - STOP Input

STOP is the input that causes immediate shutdown of the movement (fol-

lowed by a brief inversion of the manoeuvre). Devices with output featur-

ing normally open “NO” contacts, and devices with normally closed “NC” 

contacts, as well as devices with 8.2k

Ω

 constant resistance output, like 

sensitive edges, can be connected to this input.

Multiple devices, even of different types, can be connected to the STOP 

input if suitable arrangements are made; see 

Table 7

.

TABLE 7

2

nd

 device type:

1

st

 device type:

NO

NC

8,2K

Ω

NO

In parallel (

note 2

)

(

note 1

)

In parallel

NC

(

note 1

)

In series (

note 3

)

In series

8,2K

Ω

In parallel

In series

(

note 4

)

Note 1.

 NO and NC combinations are possible by placing the 2 con-

tacts in parallel, taking care to place a 8.2 k

Ω

 resistance in parallel to 

the NC contact (thus enabling the combination of 3 devices: NO, NC 

and 8.2k

Ω

).

Note 2.

 Any number of NO devices can be connected to each other in 

parallel.

Note 3.

 Any number of NC devices can be connected to each other in 

series.

Note 4.

 Only two devices with 8.2k

Ω

 constant resistance output can be 

connected in parallel; if needed, multiple devices must be connected in 

“cascade” configuration with a single 8.2 k

Ω

 terminal resistance. 

Warning! – If the STOP input is used to connect devices with safety 

functions, only the devices with 8.2K

Ω

 constant resistance output 

guarantee safety category 3.

As with the ECSbus, the control unit recognises the type of device con-

nected to the STOP input during the learning phase; subsequently the 

control unit gives a STOP command when it detects a variation with 

respect to the learned state.

9.3.3 - Recognition of other devices

The learning operation of the devices connected to the ECSbus and 

STOP input is usually carried out during the installation phase; if devices 

are added or removed the learning operation can be carried out again as 

follows:

01.

  Press the 

P2

 button 

[B] 

(

fig. 21

) on the control unit for at least three 

seconds, then release the button.

02.

  Wait a few seconds for the control unit to complete the device learn-

ing phase.

03.

  When the recognition procedure is complete, the 

P2

 

led

 

[A]

 (

fig. 21

will go off. If the 

led

 

P2

 flashes it means there is an error; see para-

graph 10.5 “Troubleshooting”.

04.

  After having added or removed a device the automation test must be 

carried out again as specified in paragraph 7.1 “Testing”.

Summary of Contents for CLB207

Page 1: ...structions et avertissements pour l installation et l utilisation EN Instructions and warnings for installation and use IT Istruzioni ed avvertenze per l installazione e l uso PL Instrukcje i ostrze e...

Page 2: ...Fran ais...

Page 3: ...ON LECTRIQUE LA LOGIQUE DE COMMANDE 7 PROGRAMMATION PHASE 6 9 6 1 RACCORDEMENT DE L ALIMENTATION LECTRIQUE 9 6 2 V RIFICATIONS INITIALES 9 6 3 RECONNAISSANCE DES DISPOSITIFS CONNECT S 9 6 4 RECONNAISS...

Page 4: ...er est en excellent tat et adapt l usage pr vu Le produit ne peut tre utilis par des personnes y compris des en fants dont les capacit s physiques sensorielles ou mentales sont limit es ou ne disposan...

Page 5: ...diqu e dans le Tableau 2 RECOMMANDATION La technologie ECSbus permet de connecter plusieurs dispositifs entre eux en utilisant entre un dispositif et l autre un PHASE 2 2 1 DESCRIPTION DU PRODUIT ET A...

Page 6: ...Entr e STOP C ble 2 x 0 5 mm2 20 m note 3 Entr e SbS C ble 2 x 0 5 mm2 20 m note 3 E Sortie moteur M1 et M2 C ble 3 x 1 mm2 10 m Note 1 Il est possible d utiliser un c ble d alimentation de longueur s...

Page 7: ...t tre plac pr s du portail et doit tre facile ment visible Il est possible de le fixer sur une surface horizontale ou sur une surface verticale Pour la connexion la borne Flash il n est pas n cessaire...

Page 8: ...3 4 5 TX RX M1 M2 Flash ECSbus Stop Open Aerial M M M M FLASH BUS STOP SbS Fuse 2A F NC NO led BUS led Stop led SbS 6 motor ducteur M1 motor ducteur M2 FL200 PH200 B M M M M marron jaune vert bleu ma...

Page 9: ...Fran ais 7 Fran ais 8 7 1 Led SAFE 3 2 4 5 mm 01 03 05 02 04 9...

Page 10: ...8 Fran ais Fran ais 6 mm x4 05 B 6 mm x4 05 A 2 1 aerial flash 2 1 06 07 08 09 02 03 04 01 10...

Page 11: ...a une erreur voir le paragraphe 9 5 R solution des probl mes La phase de reconnaissance des dispositifs connect s peut tre refaite tout moment m me apr s l installation par exemple en cas d ajout d u...

Page 12: ...10 Fran ais Fran ais N M N M FLASH BUS STOP SbS A 11 N M N M FLASH BUS STOP SbS B A C 12 N M N M FLASH BUS STOP SbS A B 15 N M N M FLASH BUS STOP SbS A B 13 14 TX RX B LED T5 T2 T4 T3 T1...

Page 13: ...oir des effets nuisibles sur l environnement et sur la sant des personnes Comme l indique le symbole ci contre il est interdit de jeter ce produit avec les ordures m nag res Proc der la col lecte diff...

Page 14: ...in portail ouvert Appuyer 3 fois sur la touche T2 D charge en fermeture moteur 1 et moteur 2 1 Aucune d charge Appuyer 1 fois sur la touche T3 2 0 1s Minimum Appuyer 2 fois sur la touche T3 3 0 2s App...

Page 15: ...cuter l action pr vue dans le Tableau 5 en fonction du param tre v rifier 04 Rel cher la touche quand le feu clignotant commence clignoter 05 Compter les clignotements et suivant leur nombre v rifier...

Page 16: ...ant que l nergie produite par le panneau photovolta que et accumul e dans la batterie reste sup rieure celle qui est consomm e par les man uvres du portail l aide d un simple calcul il est possible d...

Page 17: ...eulement deux conducteurs sur lesquels transitent aussi bien l alimentation lectrique que les signaux de communication Tous les dispositifs sont connect s en parall le sur les 2 m mes conduc teurs de...

Page 18: ...9 4 2 M morisation en Mode 2 Avec la m morisation de l metteur radio en Mode 2 il est possible d associer chaque touche l une des commandes disponibles dans le Tableau 9 En Mode 2 chaque touche n cess...

Page 19: ...tteur n est pas m moris N M N M FLASH BUS STOP SbS A B 22 TABLEAU 9 1 fois Commande Pas pas Commande l automatisme suivant la description du Tableau 3 fonction Pas pas 2 fois Commande Ouverture pi ton...

Page 20: ...d but de chaque man uvre n a pas t positif les contr ler en v rifiant galement sur le Tableau 11 La man uvre commence mais juste apr s une inversion se produit La force s lectionn e est trop basse po...

Page 21: ...t le mouvement l entr e STOP est intervenue en v rifier la cause TABLEAU 13 fig 25 Led ECSbus A tat Action teinte La led clignote lentement Anomalie V rifier si la tension arrive v rifier si les fusib...

Page 22: ...ar seconde La phase de reconnaissance n a pas t effectu e ou il y a des erreurs dans les donn es m moris es Des dispositifs pourraient tre en panne v rifier et ventuellement effectuer de nouveau la ph...

Page 23: ...m ou normale ment ferm s avec reconnaissance automatique de l tat normal une variation par rapport l tat m moris provoque la commande STOP Entr e Antenne radio 50 ohm pour c ble type RG58 ou similaire...

Page 24: ...ssentielles suivantes ont t respect es 1 1 1 1 2 1 1 3 1 2 1 1 2 6 1 5 1 1 5 2 1 5 5 1 5 6 1 5 7 1 5 8 1 5 10 1 5 11 Le producteur s engage transmettre aux autorit s nationales suite une demande d men...

Page 25: ...e Si les dispositifs de s curit sont hors service il faut faire r parer au plus t t l automatisme 11 2 Interventions d entretien autoris es l utilisateur Nous indiquons ci apr s les interventions que...

Page 26: ...Fran ais...

Page 27: ...OR 7 5 4 ELECTRICAL CONNECTION TO CONTROL UNIT 7 PROGRAMMING STEP 6 9 6 1 POWER SUPPLY CONNECTION 9 6 2 PRELIMINARY CHECKS 9 6 3 RECOGNITION OF CONNECTED DEVICES 9 6 4 RECOGNITION OF GATE LEAF OPEN AN...

Page 28: ...ing order and are suitable for the intended applica tions The product is not intended for use by persons including children with reduced physical sensory or mental capacities nor by anyone lacking suf...

Page 29: ...r using between one device and the next a single bus cable with two internal electrical conductors The connection between the devices can have a cascade a star or a mixed configuration between the fir...

Page 30: ...20 m note 3 E Motors M1 and M2 output Cable 3 x 1 mm2 10 m Note 1 You may use a cable longer than 30 m provided it has a larger gauge for example 3 x 2 5 mm2 and it is equipped with close to the auto...

Page 31: ...SHING INDICA TOR fig 10 The flashing light must be positioned near the gate in a clearly visible position It can be fasted to a horizontal or vertical surface For connection to the Flash terminal no p...

Page 32: ...1 3 4 5 TX RX M1 M2 Flash ECSbus Stop Open Aerial M M M M FLASH BUS STOP SbS Fuse 2A F NC NO led BUS led Stop led SbS 6 Gearmotor M1 Gearmotor M2 FL200 PH200 B M M M M brown yellow green blue brown y...

Page 33: ...English 7 English 8 7 1 Led SAFE 3 2 4 5 mm 01 03 05 02 04 9...

Page 34: ...8 English English 6 mm x4 05 B 6 mm x4 05 A 2 1 aerial flash 2 1 06 07 08 09 02 03 04 01 10...

Page 35: ...5 Troubleshooting The phase for learning connected devices can also be repeated at any time after installation for example if a photocell is added simply repeat the procedure from point 01 6 4 LEARNI...

Page 36: ...10 English English N M N M FLASH BUS STOP SbS A 11 N M N M FLASH BUS STOP SbS B A C 12 N M N M FLASH BUS STOP SbS A B 15 N M N M FLASH BUS STOP SbS A B 13 14 TX RX B LED T5 T2 T4 T3 T1...

Page 37: ...parts of the product may contain pollutants or hazard ous substances which if disposed of in the environment may cause seri ous damage to the environment or physical health As indicated by the symbol...

Page 38: ...1 Step by Step Press T1 once 2 pedestrian opening Press T1 twice Flash output configuration 1 Flashing light Press T2 once 2 Courtesy light Press T2 twice 3 Gate open indicator Press T2 three times M...

Page 39: ...e changed 04 Release the key when the flashing light starts to flash 05 Count the number of flashes and according to the number check the corresponding value on Table 3 Example If after pressing T1 an...

Page 40: ...te of the maximum number of cycles per day performed by the automation in a certain period of the year provided that a positive energy balance is maintained The first part of the available energy calc...

Page 41: ...us is a system that enables connections of ECSbus devices using just two wires which convey both electrical power and communication signals All devices are connected in parallel on the same 2 wires of...

Page 42: ...must first delete the transmitter by performing the procedure described in 9 4 4 Deleting a radio transmitter 02 Press P1 B fig 22 on the control unit the same number of times as your desired command...

Page 43: ...memorised transmitters 01 Press the P1 key B key fig 22 on the control unit and hold it down 02 Wait until the P1 led A fig 22 lights up then wait until it goes off then wait until it has flashed 3 t...

Page 44: ...given a positive result check them referring also to compliance with Table 11 The manoeuvre starts but it is immediately fol lowed by a reverse run The selected force could be too low for this type o...

Page 45: ...ated identify the cause TABLE 13 fig 25 ECSbus led A Status Action Off The led flashes slowly Malfunction Make sure there is power supply check to see if the fuses are blown if nec essary identify the...

Page 46: ...ed On All OK Fast speed selected 1 flash per second The device recognition phase has not been carried out or there are errors in the data saved It is possible that there are faulty devices Check and i...

Page 47: ...STOP input For normally open and or 8 2kohm constant resistance type contacts or normally closed con tacts with self learning of the normal status a variation with respect to the memorised status gen...

Page 48: ...hnical documentation has been drafted in accordance with Annex VII B of Directive 2006 42 EC and that the following essential requirements have been fulfilled 1 1 1 1 2 1 1 3 1 2 1 1 2 6 1 5 1 1 5 2 1...

Page 49: ...tion as soon as possible 11 2 User admissible maintenance operations The operations that the user must carry out periodically are listed below Cleaning of the surfaces of the devices use a slightly da...

Page 50: ......

Page 51: ...RE LAMPEGGIANTE 7 5 4 COLLEGAMENTO ELETTRICO ALLA CENTRALE 7 PROGRAMMAZIONE PASSO 6 9 6 1 ALLACCIAMENTO DELL ALIMENTAZIONE 9 6 2 VERIFICHE INIZIALI 9 6 3 APPRENDIMENTO DEI DISPOSITIVI COLLEGATI 9 6 4...

Page 52: ...are sia in ottimo stato ed adeguato all uso Il prodotto non destinato a essere usato da persone bambini com presi le cui capacit fisiche sensoriali o mentali siano ridotte oppure con mancanza di esper...

Page 53: ...tte di collegare pi dispo sitivi tra loro utilizzando tra un dispositivo e l altro un cavo bus unico con 2 conduttori elettrici interni Il collegamento tra i dispositivi pu assumere una configurazione...

Page 54: ...2 x 0 5 mm2 20 m nota 3 Ingresso SbS Cavo 2 x 0 5 mm2 20 m nota 3 E Uscita motori M1 e M2 Cavo 3 x 1 mm2 10 m Nota 1 possibile usare un cavo di alimentazione pi lungo di 30 m purch abbia una sezione m...

Page 55: ...sizionato in prossimit del cancello e deve essere facilmente visibile possibile fissarlo su una superficie orizzontale o su una superficie verticale Per il col legamento al morsetto Flash non necessar...

Page 56: ...4 5 TX RX M1 M2 Flash ECSbus Stop Open Aerial M M M M FLASH BUS STOP SbS Fuse 2A F NC NO led BUS led Stop led SbS 6 motoriduttore M1 motoriduttore M2 FL200 PH200 B M M M M marrone giallo verde blu ma...

Page 57: ...Italiano 7 Italiano 8 7 1 Led SAFE 3 2 4 5 mm 01 03 05 02 04 9...

Page 58: ...8 Italiano Italiano 6 mm x4 05 B 6 mm x4 05 A 2 1 aerial flash 2 1 06 07 08 09 02 03 04 01 10...

Page 59: ...ica che c qualche errore vedere il paragrafo 9 5 Risoluzione dei problemi La fase di apprendimento dispositivi collegati pu essere rifatta in qualsi asi momento anche dopo l installazione ad esempio s...

Page 60: ...10 Italiano Italiano N M N M FLASH BUS STOP SbS A 11 N M N M FLASH BUS STOP SbS B A C 12 N M N M FLASH BUS STOP SbS A B 15 N M N M FLASH BUS STOP SbS A B 13 14 TX RX B LED T5 T2 T4 T3 T1...

Page 61: ...isperse nell ambiente potrebbero provo care effetti dannosi sull ambiente stesso e sulla salute umana Come indicato dal simbolo a lato vietato gettare questo prodotto nei rifiuti domestici Eseguire qu...

Page 62: ...pertura 1 anta a met Premere 1 volta il tasto T2 2 Apertura 1 anta totale Premere 2 volte il tasto T2 3 Apertura 2 ante parziali a 1 4 della corsa Premere 3 volte il tasto T2 4 Apertura 2 ante parzial...

Page 63: ...ntare i lampeggi ed in base al numero verificare sulla Tabella 3 il corrispondente valore Esempio Se dopo aver premuto T1 e T2 per 5 s e poi il tasto T1 il lam peggiante effettuer tre lampeggi il temp...

Page 64: ...massimo di cicli al giorno che l automazione pu eseguire in un determinato periodo dell anno affinch questo bilancio energetico rimanga positivo La prima parte del calcolo dell energia disponibile tr...

Page 65: ...tuare i collegamenti dei dispo sitivi ECSbus con soli due conduttori sui quali transita sia l alimentazione elettrica che i segnali di comunicazione Tutti i dispositivi vengono col legati in parallelo...

Page 66: ...delle stesse re Se il led P2 lampeggia significa che c qualche errore vedere paragrafo 10 5 Risoluzione dei problemi 04 Dopo aver aggiunto o rimosso dei dispositivi necessario eseguire nuovamente il c...

Page 67: ...tore memorizzato in Modo 1 sufficiente una sola fase di cancellazione e al punto 3 pu essere premuto un tasto qualsiasi Se il trasmettitore memorizzato in Modo 2 occorre una fase di cancellazione per...

Page 68: ...o tra TX ed RX Verificare che il led sul TX esegua un lampeggio lento Verificare l allineamento TX RX TABELLA 10 fig 23 Sintomi Probabile causa e possibile rimedio l trasmettitore radio non emette alc...

Page 69: ...un intervento dell ingresso di STOP verificare la causa TABELLA 13 fig 25 Led ECSbus A Stato Azione Spento Il led lampeggia lentamente Anomalia Verificare se c alimentazione verificare che i fusibili...

Page 70: ...t veloce 1 lampeggio al secondo Non stata eseguita la fase di apprendimento dispositivi oppure ci sono errori nei dati in me moria possibile vi siano dispositivi guasti verificare ed eventualmente ese...

Page 71: ...costante 8 2kohm oppure contatti normal mente chiusi con autoapprendimento dello stato normale una variazione rispetto allo stato memorizzato provoca il comando STOP Ingresso Antenna radio 50 ohm per...

Page 72: ...006 42 CE e che sono stati rispettati i seguenti requisiti essenziali 1 1 1 1 2 1 1 3 1 2 1 1 2 6 1 5 1 1 5 2 1 5 5 1 5 6 1 5 7 1 5 8 1 5 10 1 5 11 Il produttore si impegna a trasmettere alle autorit...

Page 73: ...sicurezze fuori uso necessario far riparare quanto prima l automatismo 11 2 Interventi di manutenzione concessi all utilizzatore Di seguito sono elencati gli interventi che l utilizzatore deve eseguir...

Page 74: ...Fran ais...

Page 75: ...ZENIE ELEKTRYCZNE DO CENTRALI 7 PROGRAMOWANIE KROK 6 9 6 1 POD CZENIA ZASILANIA 9 6 2 KONTROLE POCZ TKOWE 9 6 3 WCZYTYWANIE POD CZONYCH URZ DZE 9 6 4 WCZYTYWANIE K T W OTWARCIA I ZAMKNI CIA SKRZYD A B...

Page 76: ...tan i s odpowiednie do u ycia Produkt nie jest przeznaczony do obs ugi przez osoby w tym dzieci o ograniczonych zdolno ciach fizycznych zmys owych b d umys o wych lub przez osoby nieposiadaj ce odpowi...

Page 77: ...y kolejnymi urz dzeniami jednego kabla bus z 2 wewn trznymi przewodami elektrycznymi Po czenie mi dzy urz dzeniami mo e przyj konfiguracj w formie kaskady gwiazdy lub mieszan KROK 2 2 1 OPIS PRODUKTU...

Page 78: ...abel 3 x 1 mm2 10 m Uwaga 1 Mo liwe jest u ycie kabla zasilaj cego d u szego od 30 m pod warunkiem e b dzie on posiada wi kszy przekr j np 3 x 2 5 mm2 i e w pobli u automatyki zostanie przewidziane uz...

Page 79: ...ampa musi by przymocowana w pobli u bramy i musi by widoczna Istnieje mo liwo jej zamontowania lampy na powierzchni pionowej lub poziomej W celu pod czenia do zacisku Flash nie nale y przestrzega adne...

Page 80: ...TX RX M1 M2 Flash ECSbus Stop Open Aerial M M M M FLASH BUS STOP SbS Fuse 2A F NC NO led BUS led Stop led SbS 6 motoreduktor M1 motoreduktor M2 FL200 PH200 B M M M M br zowy ty zielony niebieski br zo...

Page 81: ...Polski 7 Polski 8 7 1 Led SAFE 3 2 4 5 mm 01 03 05 02 04 9...

Page 82: ...8 Polski Polski 6 mm x4 05 B 6 mm x4 05 A 2 1 aerial flash 2 1 06 07 08 09 02 03 04 01 10...

Page 83: ...wnie po zako czeniu monta u na przyk ad je eli zostanie dodana fotokom rka wystarczy j powt rzy od punktu 01 6 4 WCZYTYWANIE K T W OTWARCIA I ZAMKNI CIA SKRZYDE BRAMY Po wczytaniu urz dze nale y umo...

Page 84: ...10 Polski Polski N M N M FLASH BUS STOP SbS A 11 N M N M FLASH BUS STOP SbS B A C 12 N M N M FLASH BUS STOP SbS A B 15 N M N M FLASH BUS STOP SbS A B 13 14 TX RX B LED T5 T2 T4 T3 T1...

Page 85: ...egorii produktu Uwaga niekt re elementy produktu mog zawiera substancje szko dliwe lub niebezpieczne kt re pozostawione w rodowisku mog yby zaszkodzi rodowisku lub zdrowiu ludzkiemu Jak wskazuje symbo...

Page 86: ...iate ko nocne Nacisn 2 razy przycisk T2 3 Kontrolka otwarta brama Nacisn 3 razy przycisk T2 Roz adunek podczas zamykania Silnik 1 i Silnik 2 1 Brak roz adunku Nacisn 1 raz przycisk T3 2 0 1s Minimalny...

Page 87: ...ia Standby Gdy centrala otrzyma polecenie przywraca normalne dzia anie z niewielkim op nieniem Celem tej funkcji jest ograniczenie zu ycia co jest wa n kwesti przy zasilaniu z akumulatora 9 2 2 Instal...

Page 88: ...j liczby cykli w ci gu dnia kt r automatyka mo e wykona w okre lonym okresie roku by bilans energetyczny pozosta dodatni Pierwsza cz obliczenia dost pnej energii jest opisana w instrukcji baterii s on...

Page 89: ...DZE W razie konieczno ci istnieje mo liwo dodawania lub usuwania dodat kowych urz dze w dowolnym momencie Uwaga Nie dodawa innych urz dze przed sprawdzeniem ich zgodno ci z central i sterowanym przez...

Page 90: ...usuni ciu urz dze pod czonych mo na powt rzy wczytywanie wy cznie tych urz dze w nast puj cy spos b 01 Na centrali nacisn i przytrzyma wci ni ty przez przynajmniej trzy sekundy przycisk P2 B rys 21 n...

Page 91: ...nia i nacisn w punkcie 3 dowolny przycisk Gdy nadajnik by wczytany w Trybie 2 ka dy wczytany przycisk nale y wykasowa oddzielnie 01 Nacisn i przytrzyma wci ni ty przycisk P1 B rys 22 na cen trali 02 O...

Page 92: ...okom rek wykonywany na pocz tku ka dego manewru nie powi d si Sprawdzi fotokom rki pos uguj c si r wnie Tabel 11 Manewr rozpoczyna si ale zaraz po tym nast puje zmiana kierunku ruchu Wybrana si a jest...

Page 93: ...o wej cie STOP sprawdzi przyczyn TABELA 13 rys 25 Dioda led ECSbus A Stan Czynno Zgaszona Dioda led miga powoli Usterka Sprawdzi obecno zasilania sprawdzi czy nie zadzia a y bezpieczniki ewentualnie...

Page 94: ...lno wieci si Wszystko OK Wybrana pr dko szybko 1 migni cie na sekund Nie zosta a wykonana procedura rozpoznawania urz dze lub wyst puj b dy w danych w pami ci Mo liwe e nast pi a usterka urz dze spraw...

Page 95: ...w normalnie otwartych i lub sta ego oporu 8 2k lub dla styk w normalnie zamkni tych rozpoznawany jest stan normalny ka da zmiana zapisanego stanu wywo a polecenie STOP Wej cie dla anteny radiowej 50...

Page 96: ...B dyrektywy 2006 42 WE oraz e spe nione zosta y nast puj ce wymagania podstawowe 1 1 1 1 2 1 1 3 1 2 1 1 2 6 1 5 1 1 5 2 1 5 5 1 5 6 1 5 7 1 5 8 1 5 10 1 5 11 Producent zobowi zuje si do przekazania w...

Page 97: ...k najszybciej naprawi elementy automatyki 11 2 Konserwacja do wykonania przez u ytkownika Poni ej wymienione zosta y czynno ci kt re u ytkownik bramy powinien okresowo wykonywa Do czyszczenia powierzc...

Page 98: ...com Service Apr s Vente France En cas de panne merci de contacter obligatoirement notre Service Apr s Vente par t l phone ou par email 0 820 859 203 Service 0 15 min prix appel niceservice niceforyou...

Reviews: