30
www.climacoolcorp.com
0000
0000
�l:1�1:1�
MODULE PD\./ER FEED
208-230/460/575V 3PH
0000
�l:1�1:1�
[
MAIN PD\./ER FEED
208-230/460/575V 3PH
115V-1PH
TYPICAL
BREAKER PANEL
(6,0 AMpS MlnlMUM)
--------------7
I
I
I
I
i
i
i
i
i
i
i
i
i
i
i
i
ARC1S6 DA TA C□MMUNICA TI□N IJIRING
i
C□NTR□L
PANEL
11�:
1�:
•.;.11
a ■ a
•
j_ ___________________ .1...u..1-._j ____________________ J_J!..1.-._j ____________________ _
C2-C□NDUCT□R SHIELDED CABLE)
A
j
-·-·-·-·-·-·-·-·-·-·-·-·-·-·-·-·-·-·-·-·-·-·-·-·-·-·tJ-·-·-·-·-·-·-·-·_J
PLEASE REFER T□ THE MASTER PANEL IJIRING DIAGRAM F□R DETAILED INF□RMATI□N
□N IJIRING THE FL□IJ SENS□R/SIJITCHES, TEMPERATURE SENS□RS, ETC,
------ CHILLER P□IJER IJIRING C208-230/460V 3PH)
------- C□NTR□LLER P□IJER IJIRING C11SV-1PH)
-·-·-·-·-·-·-·- DATA C□MMUNICATI□N IJIRING C2-C□NDUCT□R SHIELDED CABLE)
coor;
THE ULTIMATE CHILLER
SOLUTION
®
This document is the sole property of ClimaCool
Corp. Distribution of this document is forbidden
without the written consent of ClimaCool Corp.
Design changes to any portion of this document
may occJJL without notice.
CHILLER LAYOUT:
CC P /N's:
PROJECT:
SIZE
I
FSCM NOj DWG NO.
CCE-GENERIC SIMULTANE□US HTG & CLG BANK C□NTR□L IJIRING
SCALE
DATE
08/29/2011
SHEET
REV. A
Power Distribution Drawing
Notes:
1 .
Breaker panel represents field power supply and is to be installed by others.
Not provided as part of the ClimaCool modular chiller system .
2 . Breaker panels can be supplied for skid mount packages or new construction
projects as options . Consult the local ClimaCool Representative .
3 . Control wiring by others .
4 .
Field connections are simplified requiring only a two-conductor shielded cable
daisy chain from the master controller to the modules (see Figure 18) .
Figure 17
Specifications for ARC156 Wiring
• Description - Single twisted pair, low capacitance, CL2P,
TC foam FEP, plenum rated cable
• Conductor - 22 AWG (7x30) stranded copper (tin plated)
0 .0 .0 in . (0 .762mm) O .D .
• Insulation – Foamed FEP, 0 .015 in . (0 .381mm) wall,
0 .060 in . (1 .524mm) O .D .
• Twist Lay – 2 in . (50 .8mm) lay on pair, 6 twists/foot
(20 twists/meter) nominal
• Shielding – Aluminum/Mylar shield with 24 AWG (7x32)
TC drain
• DC Resistance – 15 .2 Ohms/1000 feet (50 Ohms/km)
nominal
• Capacitance – 12 .5 pF/ft (41 pF/meter) nominal conductor
to conductor
• Characteristic Impedance – 100 Ohms
Cable Shields
Do not ground the shield to earth ground or to the control
module’s power ground . The PROT485 and the individual
control modules allow the shield to float a limited amount
so that there are no ground loops . If the voltage on the
shield becomes too great relative to the earth ground, then
the excess voltage is bled off with protective devices on the
PROT485 or on the control modules .
Noise Avoidance
Avoid running communication wires or sensor input wires
next to AC power wires or the control module’s relay output
wires. These can be a source of noise that can affect
signal quality .
Common sources of noise are:
Spark ignitors
Induction heaters
Radio transmitters
Large contactors (ex .motor starters)
Variable speed drives Video display devices
Electric motors (> 1hp) Lamp dimmers
Generators
Fluorescent lights
Relays
Parallel runs with power lines
Transformers
Other electronic modules
If noise is a problem and you cannot move the wiring,
use ferrite clamp-on chokes on the cabling to improve
signal quality .
Figure 18
Summary of Contents for CLIMACOOL UCR 30
Page 19: ...17 www climacoolcorp com Voltage Phase Monitor Wiring Diagram...
Page 29: ...27 www climacoolcorp com Evaporator Water Pressure Drop Charts...
Page 30: ...28 www climacoolcorp com Glycol Performance Adjustments Factor Charts...
Page 78: ...76 www climacoolcorp com Wiring Diagram...
Page 79: ...77 www climacoolcorp com Wiring Diagram...
Page 80: ...78 www climacoolcorp com Wiring Diagram CoolLogic Control Panel...
Page 81: ...79 www climacoolcorp com Wiring Diagram CoolLogic Control Panel...