Changing Data Logger Transmission Interval
The Transmit Interval in the Device Remote Configuration Tool determines how often a data logger will
power up its telemetry to contact the WQData LIVE Web Datacenter. On each transmission, the data logger will:
Upload all newly logged data.
Process all settings changes listed in the Command Queue.
To update data logger transmit intervals in WQData LIVE:
tool within the administrator settings.
a. Select the site and desired data logger to make adjustments.
2. In the Transmit Interval section, enter the desired frequency in the New Value field.
a. Intervals are entered in minutes with an accepted value range of 5 to a maximum of 1440 minutes (1
day)
b. Note: Transmit frequency changes will impact system power consumption. Verify the selected value is
sustainable given the telemetry type and power source prior to adjusting the interval for solar-charged
systems.
3. Scroll to the bottom of the menu and click SAVE.
a. A success prompt should appear.
4. Following the data logger’s next transmission to WQData LIVE, the transmission change will be applied and
the Current Value field for the Transmit Interval will update.
Enter the updated Transmit Interval value.
Transmission interval update successfully applied.
70
Summary of Contents for X2-CB
Page 11: ...Select sensors from drop down list 11...
Page 17: ...Cellular X2 C to WQData LIVE 17...
Page 18: ...Iridium X2 I to WQData LIVE 18...
Page 19: ...Radio to Cellular X2 RC to WQData LIVE 19...
Page 48: ...Iridium X2 data flow 48...
Page 94: ...Rotate the antenna bushing counterclockwise to remove the antenna 94...
Page 108: ...13 Remove the Main SD Card Main SD Card Location 108...