VS300 Operations and Maintenance Manual
Operating the transmitter
Issue 8.0 2016-03-01
Page 2-171
Site Control Settings
You can use the AUI’s
Site Control
page (see
) to locally or remotely configure remote
inputs and outputs for use with external site control equipment (air conditioner, etc.). This page
allows the user to create and configure custom inputs and outputs and assign them for use using the
Remote Inputs
and
Remote Outputs
pages.
To view this page, select
Remote I/O
from the
Menu
options and select the
Site Control
tab. Press
X
in the upper, right corner to close this page and return to the
Home
page.
Figure 2.145: Remote I/O Page - Site Control
Adding or Editing a Site Control Rule
Selecting the
Add
or
Edit
button displays the rule editing window (see
)
for site control inputs and outputs. This window allows you to create a new site control rule or edit an
existing one. Each custom input or output can be assigned a name, severity level and trigger
parameters (active state and time delay). Each rule can also be set to latch (i.e., requiring a reset) or log
with the rest of the transmitter’s alarm and status signals, upon its occurrence. You can use Boolean
logic expressions to perform ‘AND’, ‘OR’ and ‘XOR’ (exclusive OR) functions on multiple inputs or
rules.
Use the
Edit Site Control Rule
window as follows: