86
NATIONAL
INSTRUMENTS
Model Rated Output
Voltage (V)
Minimum (V) Maximum (V)
20
1.0
24.0
36
2.0
40.0
60
5.0
66.0
100
5.0
110
Table 7-9: OVP programming range
Model Rated Output
Voltage (V)
Minimum (V) Maximum (V)
20
0
19.0
36
0
34.2
60
0
57.0
100
0
95.0
Table 7-10: UVL/UVP programming range
Model
Minimum (A)
Maximum (A)
20-10
00.0000
10.0000
36-6
0.00000
6.00000
60-3.5
0.00000
3.50000
100-2
0.00000
2.00000
Table 7-6: RMX-4101 models Current programming range
and communication response format
Model
Minimum (A)
Maximum (A)
20-20
00.0000
20.0000
36-12
00.0000
12.0000
60-7
0.00000
7.00000
100-4
0.00000
4.00000
Table 7-7: RMX-4102 models Current programming range
and communication response format
Model
Minimum (A)
Maximum (A)
20-40
00.0000
40.0000
36-24
00.0000
24.0000
60-14
00.0000
14.0000
100-8
00.0000
8.00000
Table 7-8: RMX-4104 models Current programming range
and communication response format
NOTE:
The power supply can accept values higher by 5% than the table values, however it is not recommended
to program the power supply over the rated values.
NOTE:
The UVP protection starts operating for values higher than 5% of Rated Output Voltage.