20
NA
TIONAL
INSTRUMENTS
2.2 RMX-4102 Series Specifications
RMX-4102
MODEL
N/A
20-20
36-12
60-7
100-4
1. Rated output voltage(*1)
V
20
36
60
100
2. Rated output current (*2)
A
20
12
7
4
3. Rated output power
W
400
432
420
400
CONSTANT VOLTAGE MODE
20-20
36-12
60-7
100-4
1. Max. Line regulation (*6)
---
0.01% of rated output 2mV
2. Max. Load regulation (*7)
---
0.01% of rated output 2mV
3. Ripple and noise (p-p, 20MHz) (*8)
mV
50
50
50
80
4. Ripple r.m.s. 5Hz~1MHz
mV
6
6
7
8
5. Temperature coefficient
PPM/°C
30PPM/°C from rated output voltage, following 30 minutes warm-up.
6. Temperature stability
---
0.02% of rated Vout over 8hrs. interval following 30 minutes warm-up. Constant line, load & temp.
7. Warm-up drift
---
Less than 0.05% of rated output 2mV over 30 minutes following power on.
8. Remote sense compensation/wire
V
1
2
3
5
9. Up-prog. Response time, 0~Vomax.(*9)
mS
30
30
50
50
10. Down-prog. response time:
Full load (*9)
mS
10
15
30
50
Time delay (*17)
250
320
380
1200
No load (*10) (*15) (*17)
65
85
100
250
No load (*10) (*16) (*17)
200
290
310
1100
11. Transient response time
mS
Time for output voltage to recover within 0.5% of its rated output for a load change 10~90% of rated output current.
Output set-point: 10~100%, Local sense.
Less than 1mS, for models up to and including 100V
12. Hold-up time (*19)
---
16mSec Typical.
CONSTANT CURRENT MODE
20-20
36-12
60-7
100-4
1. Max. Line regulation (*6)
---
0.01% of rated output 2mA
2. Max. Load regulation (*11)
---
0.01% of rated output 5mA
3. Load regulation thermal drift
---
Less than 0.05% of rated output current over 30 minutes following load change.
4. Ripple r.m.s. 5Hz~1MHz
mA
40
15
8
3
5. Temperature coefficient
PPM/°C
100PPM/°C from rated output current, following 30 minutes warm-up.
6. Temperature stability
---
0.05% of rated Iout over 8hrs. interval following 30 minutes warm-up. Constant line, load & temperature.
7. Warm-up drift
---
Less than +/-0.1% of rated output current over 30 minutes following power on.
PROTECTIVE FUNCTIONS
20-20
36-12
60-7
100-4
1. Foldback protection
---
Output shut-down when power supply change mode from CV to CC or CC to CV. User presetable.
Reset by AC input recycle in autostart mode or by OUTPUT button or by rear panel ENABLE, or by communication port.
2. Over-voltage protection (OVP)
---
Inverter Shut down method. Reset by AC input recycle in autostart mode or by OUTPUT button or by rear panel ENABLE,
or by communication port.
3. Over - voltage trip point
V
1~24
2~40
5~66
5~110
4. Output under voltage limit (UVL)
---
Preset by front panel or communication port. Prevents from adjusting Vout below limit. Does not affect in analog programming.
5. Output under voltage protection (UVP)
---
Output shut-down when power supply output voltage goes below UVP programming. User presetable.
Reset by AC input recycle in autostart mode or by OUTPUT button or by rear panel ENABLE, or by communication port.
6. Over temperature protection
---
User Selectable. Latched or non latched