MDEC – Functions
Control functions
Following engine functions are controlled:
• Engine start
• Engine stop
• Emergency start
• Restart response
• Sequences with activated “Override” function (safety system bypass).
• Nominal speed switching between two set values (optional operation as 50 Hz or 60 Hz genset).
• Injection quantity as a function of engine loading and speed.
Engine start
The starting sequence is controlled by the software integrated in the engine governor as follows.
1. Engine start
2. Start lockout time t>16 seconds.
• Starting terminated if start lockout time is t<16.
3. Start interlock.
• Start terminated if start interlock applied.
4. Emergency air-shutoff flaps open.
• Start terminated if emergency air-shutoff flaps closed.
.
5. Starter on.
6. Speed n>n1 (configurable) reached within t1 (configurable).
• Start terminated if speed is n<n1 within t1. Start speed is too low “Start speed low”.
.
7. Start injection quantity
8. Speed n>300 reached within t2 (configurable).
• Start terminated if speed is n<300 within t2 (configurable). Start speed is too low “Run up speed low”.
9. Starter off.
10. Idling speed reached.
• Start terminated if idling speed not reached, “Idle speed low”.
11. Engine running at idling speed.
Restart response
The response of the engine is determined by the following factors on receiving a start request
when the engine is running down following a stop command:
• The engine immediately runs up to nominal speed if the engine speed is > 80 rpm;
• the engine is shut down if the engine speed is < 80 rpm. Restarting is only possible
on expiry of the start lockout time.
Emergency start
The following start interlock criteria are bypassed when override is active on starting the engine:
• Low coolant temperature (configurable).
• High coolant temperature (configurable).
• Coolant level (configurable).
Engine stop
An engine stop is tripped by activation of binary input BE1 at the engine governor or by the engine
protection system. Fuel is no longer injected as injector activation is disrupted.
Any starting procedure which has been initiated is interrupted.
Override (safety system bypass)
The “Override” feature is used to bypass safety functions tripped by limit value violations or
sensor faults and to bypass start interlocks.
Operating states which would normally lead to engine shutdown are ignored when the “Override” function is
activated. The following operating states can also be configured to shut the engine down in override mode:
• Coolant level
• Coolant temperature
MS15009/00E 06-09
© MTU
Summary of Contents for Detroit Diesel 12 V 2000 P62
Page 18: ...14 Safety MS15009 00E 06 09 MTU...
Page 62: ...58 Operation MS15009 00E 06 09 MTU...
Page 188: ...184 Engine Governor Assignment and Circuitry MS15009 00E 06 09 MTU...
Page 196: ...192 Special Tools Part No Designation Use Qty F30025897 Socket wrench 1 MS15009 00E 06 09 MTU...
Page 198: ...194 Special Tools MS15009 00E 06 09 MTU...
Page 204: ...200 Annex MS15009 00E 06 09 MTU...
Page 208: ......