172
Engine Governor Assignment and Circuitry
Outputs
Observe max. output current-carrying capacity.
TAA1 Emergency stop
Transistor output for emergency stop.
TAA2 Automatic engine stop
Transistor output for automatic engine stop.
TAA3 Combined alarm
All warning messages (Limit1) are indicated here as a
combined alarm.
TAA4 n > 300
Indication of engine speed > 300 rpm.
TAA5 SS T-coolant
Shutdown, coolant temperature too high.
TAA6 SS P-lube oil
Shutdown, lube oil pressure too low.
Analog MDEC inputs
IEU1 = 0 to 10 V or 4 to 20 mA
It is possible to activate different analog desired speed
settings for the MDEC governor.
Default setting:
• Characteristic curve 71 (50 Hz) in MDEC governor
0 to 10 V activated.
Parameterized desired speed setting 4 to 20 mA must
be changed if desired.
Same applies to characteristic curve 72 (60 Hz).
MS15009/00E 06-09
© MTU