Simulating power failure (emergency): SAT
1.
Switch on fuel treatment system (→ Page 70).
2.
3.
Run engine at idling speed.
4.
Switch off pump (21) at switchgear cabinet (20).
Result:
The engine-mounted fuel delivery pump draws fuel via bypass (2) directly from tank (24).
5.
Check suction pressure at the engine-mounted fuel delivery pump.
Note:
If the suction pressure is within the admissible limits and engine operation is satisfactory.
6.
Operate engine at full load and monitor suction pressure.
Result:
Simulation was successful if the suction pressure is within the specified limits.
MS150123/01E 2017-05
| Operation | 69
TIM-ID: 0000015773 - 007