182 – AL CAN Wrong Parameters
Red alarm.
Associated parameter 2.0500.682
Cause
Corrective action
Wrong parameter value entered in
data record.
u
Contact Service. (Configuration fault)
183 – AL CAN No PU-Data
Red alarm.
Associated parameter 2.0500.683
Cause
Corrective action
A CAN mode has been selected
that initiates communications
with the help of the PU data
module. However, the necessary
PU data module is not present or
is invalid.
u
Contact Service. (Configuration fault)
184 – AL CAN PU-Data Flash Error
Red alarm.
Associated parameter 2.0500.684
Cause
Corrective action
A program error occurred while
trying to copy a received PU data
module to the flash module.
u
Contact Service. (Configuration fault)
186 – AL CAN1 Bus Off
Yellow alarm.
Associated parameter 2.0500.686
Cause
Corrective action
CAN controller 1 is in “Bus-Off”
status. Automatic switching to
CAN bus 2. Bus nodes (ECU, SAM
or EMU) faulty.
u
Check operation of nodes and cabling.
187 – AL CAN1 Error Passive
Yellow alarm.
Associated parameter 2.0500.687
Cause
Corrective action
CAN Controller 1 has signaled a
warning. Bus nodes (ECU, SAM or
EMU) are faulty.
u
Check operation of nodes and cabling.
114 | Troubleshooting | MS150098/03E 2018-04