1.4550.041 – A - PWM Position Demand Failed
Yellow alarm. Initiated by ProAct of cylinder bank A.
Cause
Corrective action
ProAct setting is not correct.
u
Check setting.
1.4550.042 – A - CAN Position Demand Failed
Red alarm. Initiated by ProAct of cylinder bank A.
Cause
Corrective action
Position specification not received
or received too late
u
Check cabling and setting.
1.4550.043 – A - CAN Fault (CAN Bus Off, CAN Ad
Red alarm. Initiated by ProAct of cylinder bank A.
Cause
Corrective action
CAN bus connection faulty.
u
Check cabling and setting.
1.4550.044 – A - CAN Stop Command
Yellow alarm. Initiated by ProAct of cylinder bank A.
Cause
Corrective action
“Stop” demand received via CAN
bus
u
Check setting.
1.4550.131 – B - Internal Fault
Red alarm. Initiated by ProAct of cylinder bank A.
Cause
Corrective action
Hardware not ready for operation.
u
Restart ProAct.
1.4550.132 – B - Stop commanded (Run/Stop)
Yellow alarm. Initiated by ProAct of cylinder bank A.
Cause
Corrective action
ProAct setting is not correct.
u
Check setting.
1.4550.133 – B - Input (Supply) Voltage Fault
Yellow alarm. Initiated by ProAct of cylinder bank A.
Cause
Corrective action
Upper or lower supply voltage
limit reached.
1. Check supply voltage.
2. Check cabling.