USER MANUAL SWG
Page 54 of 129
Connection of the external control via 4-20 mA input signals
The signal inputs built a 4-bit binary number: I4 I3 I2 I1: 0-11 mA=open=0;
11/12-20 mA=closed=1.
Status of
external signal
source
Status number
Description
I4 I3 I2
I1
-
-
0
0
0
0
0
Automatic sampling point switching
0
0
0
1
1
Analyzer is sampling the point SP1 (*1, *2)
0
0
1
0
2
Analyzer is sampling the point SP2 (*1, *2)
0
0
1
1
3
Analyzer is sampling the point SP3 (*1, *2)
0
1
0
0
4
Analyzer is sampling the point SP4 (*1, *2)
0
1
0
1
5
Analyzer is sampling the point SP5 (*1, *2)
0
1
1
0
6
Analyzer is sampling the point SP6 (*1, *2)
0
1
1
1
7
Analyzer is sampling the point SP7 (*1, *2)
1
0
0
0
8
Analyzer is sampling the point SP8 (*1, *2)
1
0
0
1
9
Analyzer is sampling the point SP9 (*1, *2)
1
0
1
0
10
Analyzer is sampling the point SP10 (*1, *2)
1
0
1
1
11
-
1
1
0
0
12
Purge phase for H2S-low-sensor**
1
1
0
1
13
Auto-Calibration
1
1
1
0
14
Remote reset of all system alarms
1
1
1
1
15
-
**only SWG100-BIO analyzers.
-
-
-
-
I
4
+
I3
I2
I1
+
+
+
Summary of Contents for SWG 100 SYNGAS
Page 1: ...SWG 100 SYNGAS USER MANUAL ...
Page 12: ...USER MANUAL SWG Page 12 of 129 11 H3PO4 inlet G1 8 inner thread ...
Page 24: ...USER MANUAL SWG Page 24 of 129 ...
Page 32: ...USER MANUAL SWG ...
Page 63: ...USER MANUAL SWG Page 63 of 129 Detail A Alarm Relais ...
Page 89: ...USER MANUAL SWG Page 89 of 129 8 3 Description of the analyser 1 1 1 1 2 ...
Page 99: ...USER MANUAL SWG Page 99 of 129 ...
Page 110: ...USER MANUAL SWG Page 110 of 129 12 Appendix ...
Page 114: ...USER MANUAL SWG Page 114 of 129 ...
Page 116: ...USER MANUAL SWG Page 116 of 129 Positions of the components 3 4 ...
Page 127: ...USER MANUAL SWG Page 127 of 129 ...
Page 129: ...USER MANUAL SWG Page 129 of 129 ...