Fault Alarms
– There are various types of fault which can be selected to trip a unique alarm or in
combination with a trip or rate of change alarm.
Input Saturation
is set when the input signal exceeds 110% of calibrated input range.
SPA
2
Failure
is set when there is self diagnosed failure of the unit.
Input/Sensor Failure
is set when there is a broken wire on a sensor or an input falls below a set
threshold.
Out of Range
can be set to detect when the input signal goes outside a user specified range (same
as band alarm) threshold. When setting the Out of Range Alarm, the values in Lower Point must be
greater than those of the Sensor Lower Limit, and less than those set in Lower Range. When setting
the Upper Point, the value must be less than the Sensor Upper Limit, and greater than those set in
Upper Range.
Programmable Limit Alarm Trips
SPA
2
SECTION 1