Programmable Limit Alarm Trips
SPA
2
SECTION 4
Main Menu/View Settings
Figure 4.2 gives an overview of the Main menu; the View menu is shown in Figure 4.3.
Upon power-
up, the SPA
2
defaults to a display of the measured value. Pressing the
DOWN
button accesses a
series of displays that show, in succession, some of the settings currently stored in unit memory.
Depending upon whether or not the Security Jumper has been installed (Figure 4.0), pressing
SELECT
will access either the first screen in the main configuration menu, “CONFG INPUT”
(or “CONFG SENSR”), or the password code query screen, “ENTER PASS”.
Once the Main Menu has been accessed, the
DOWN
button is used to move through all of the sub-
menus in a loop. Pressing the
SELECT
button accesses the first screen of the sub-menu shown on
the LCD.
Security Settings
The SPA² password security feature limits access to the front panel configuration. The password se-
curity feature is intended only to prevent the casual user from upsetting the function of the SPA2 by
inadvertently pressing the front panel push buttons. It is controlled by a single jumper inside the top
of the unit housing. You will need to remove the top cover in order to access the jumper. The pass-
word jumper setting will default to Password Required (Pins 1 and 2).
The default security password is 55. This is valid until the password is changed to another value.
Password
This menu is bypassed if the Password Security Jumper is not installed. If the jumper is installed,
the menu comes up when
SELECT
is pressed from the display of the process variable input. To
access the security jumpers, you must remove the top cover. The menu is shown as part of Figure
4.2. Refer to the
Password Configuration
section of this manual for a more detailed description of the
password feature.
1. If the jumper is installed, pressing
SELECT
from the display of the process variable input will
bring up the “ENTER PASS” screen.
2. Press
SELECT
again to enter the “PASS” screen. Use the
UP
and
DOWN
buttons to enter
“55”, the default screen for this point in the menu.
3. If a password has been set (four characters, maximum), use the
UP
or
DOWN
buttons to
display the correct password.
When the correct password number is displayed, press
SELECT
.
Note:
If the correct password is not known, the unit settings can be viewed, but not changed.
4. If you have entered the correct password, the input configuration menu, “CONFG SENSR”
(or
“CONFG SENSR”)
, will be accessed. If not, the display will show a “VIEW ONLY” message.
5. From “VIEW ONLY”, press
SELECT
to go back to the process variable input. Use the
UP
and
DOWN
buttons to view the settings in the various menus. The “VIEW ONLY” mode locks out
any attempt to make changes to the settings.
Note:
The menu to set or change the password stored in SPA
2
memory is presented in the
Password Configuration section of the manual.