Programmable Limit Alarm Trips
SPA
2
SECTION 5
Analog Output
If your instrument is equipped with the -AO option, proceed with the following instructions:
Process Variable Range–
Displays the selected process variable range in the “Measurement Mode”
section of the
Input
screen.
Output Range–
Sets your output limits.
Set your Output Range. Enter a low and high value .
Damping–
Output Damping allows you to introduce a delay (0-30sec) into the response of your unit
in order to stop short-lived spikes from setting off alarms.
Select “Enabled” if you choose to use Damping.
Enter your damping time into the “Damping” text box.
Fail Mode–
In the case of an input failure, you have the ability to set a mode you choose to alert of
the failure.
High/Low–
Choosing either of these options will send the output to a High (23.6mA for current; 11.0V
for voltage) or Low (3.6mA for current; -0.5V for voltage) fail mode, respectively.
Hold Last (TPRG) –
This will display the last value present before the failure.
Hold Go-Hi/Hold Go-Lo (TPRG) –
This will hold the last value before failure, for a set time,
and then return to the High or Low value, depending on configuration.
Note:
Once you have configured all parameters, download to the unit by selecting “Download” in the
Transfer dropdown menu located in the Status Bar. Or, click the button in the Tool Bar.